Analog Input Terminal Connections; Analog Input 1; Analog Input 2 - Siemens bt300 Operator's Manual

Hvac drive
Hide thumbs Also See for bt300:
Table of Contents

Advertisement

Chapter 2 - Control Board Terminal Connections

Analog Input Terminal Connections

Analog Input Terminal Connections
The BT300 HVAC Drive consists of two analog inputs built on Slot A. When using analog inputs, the DIP switches
must be correctly set and the analog inputs correctly configured before enabling them.
When using an analog input for speed reference, the signal is automatically scaled for Minimum Frequency (P3.3.1)
to Maximum Frequency (P3.3.2) in accordance with the signal range (for example, on a 0 to 10 Vdc signal, 0V
represents Minimum Frequency and 10V represents Maximum Frequency). This scaling can be modified. See the
analog input parameters listed in

Analog Input 1

By default, Analog Input 1 is configured for a 0 to 10 Vdc signal source. The wiring is shown below. See Figure 5
for the location of the AI1 DIP switch. The DIP switch is set to the U (voltage) position at the factory. AI1 Signal
Range (P3.5.2.3) is used for programming the signal range of the analog input. Possible settings are 0 to 10 Vdc/0
to 20 mA or 2 to 10 Vdc/4 to 20 mA.

Analog Input 2

By default, Analog Input 2 is configured for a 4 to 20 mA signal source. The wiring is shown below. See Figure 5
for the location of the AI2 DIP switch. The DIP switch is set to the I (current) position at the factory. AI2 Signal
18 | 180
Siemens Industry, Inc.
Building Technologies
Figure 5: I/O-Related DIP Switches.
Chapter 3
.
Figure 6: Analog Input 1 Terminal Connections.
Siemens BT300 HVAC Drive
DPD01809
2016-06-07

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents