Siemens bt300 Operator's Manual page 155

Hvac drive
Hide thumbs Also See for bt300:
Table of Contents

Advertisement

Code
Parameter
P5.9.2.2.1.5
Illegal data values
P5.9.2.2.1.6
Slave device busy
P5.9.2.2.1.7
Memory parity error
P5.9.2.2.1.8
Slave device failure
P5.9.2.2.1.9
Last fault response
P5.9.2.2.1.10
Control word
P5.9.2.2.1.11
Status word
MONITORING VALUES (Connection 3, Monitoring)*
M5.9.2.2.1.1
Fieldbus protocol status
M5.9.2.2.1.2
Communication status
M5.9.2.2.1.3
Illegal functions
M5.9.2.2.1.4
Illegal data addresses
*Only displays after a connection has been established.
Modbus TCP Settings
Common Settings
Connection limit (P5.9.2.1.1)
Defines how many clients can access the server simultaneously.
Unit identifier number (P5.9.2.1.2)
The Modbus slave address field usually used on Modbus Serial Line is replaced by a single byte Unit Identifier.
On TCP/IP, the Modbus server is addressed using its IP address; therefore, the Modbus Unit Identifier is not used.
Communication time out number (P5.9.2.1.3)
Modbus initiates a communication error if the Ethernet connection is lost. Communication time-out parameters
define the minimum delay between packages received from the client. The timer is reset and started after each
received package. This parameter can be used if the client is periodically polling the slaves.
Modbus TCP Monitoring Values
These values only display after a connection has been established.
Connection 1
Fieldbus protocol status (P5.9.2.2.1.1)
The Fieldbus Protocol Status provides the status of the protocol.
Siemens Industry, Inc.
Building Technologies
Min
Max
Unit
0
0
0
0
0
hex
hex
1
3
0.0
99.999
0
0
Siemens BT300 HVAC Drive
Chapter 4 - Parameters and Menu Structure
I/O and Hardware (M5)
Default
ID
Illegal data values
2464
See
(P5.9.2.2.1.5)
Slave device busy
2465
See
(P5.9.2.2.1.6)
2466
See
Memory parity error
(P5.9.2.2.1.7)
Slave device failure
2467
See
(P5.9.2.2.1.8).
Last fault response
2468
See
(P5.9.2.2.1.9)
Control Word Bits.
2469
See
Status Word Bits.
2470
See
2471
1 = Stopped
2 = Operational
3 = Faulted
0.0
2472
0-99 Number of messages with
errors.
0-999 Number of messages
without communication errors.
Illegal functions
2473
See
(P5.9.2.2.1.3)
Illegal data addresses
2474
See
(P5.9.2.2.1.4)
Description
.
.
.
.
.
.
155 | 180
DPD01809
2016-06-07