Page 2
Copyright Notice Notice Document information is subject to change without notice by Siemens Industry, Inc. Companies, names, and various data used in examples are fictitious unless otherwise noted. No part of this document may be reproduced or transmitted in any form or by any means, electronic or mechanical, for any purpose, without the express written permission of Siemens Industry, Inc.
Reference Documents How to Use this Manual About This Manual This manual is written for the owner and user of the Siemens BT300 Bypass. It is designed to help you become familiar with the Siemens BT300 Bypass and its applications.
Page 6
Serious injury, death, or severe equipment damage could occur if a procedure or instruction is not followed as specified. Le non respect d'une procédure ou instruction peut provoquer des blessures graves voir mortelles ou endommager l'équipement. Siemens Industry, Inc. BT300 Bypass Operator's Manual DPD01391 2016-08-05...
Safety Instructions The following guidelines are provided for your safety, to prevent damage, and to extend the service life of the BT300 Drive and any connected equipment. Read this information carefully. Specific Warnings, Cautions, and Notes are provided in the relevant sections of this manual.
Page 9
Safety Instructions WARNING Le variateur Siemens BT300 utilise des tensions dangereuses et commande des pièces mécaniques rotatives potentiellement dangereuses. ● Le non-respect des avertissements et des instructions contenus dans ce manuel peut occasionneré la mort de personnes, des blessures graves, ou des dommages sérieux aux biens et aux équipements.
During bypass operation, the bypass contactor provides the ability to operate the motor on utility power and eliminate the BT300 Drive from the motor control circuit. Figure 1: Bypass Contactor Options. The Siemens BT300 Bypass consists of a BT300 Drive and a bypass enclosure with controls that include the following: ●...
Page 11
The motor is connected to utility/line power. ● Auto-Bypass (electronic only) – Requires to be enabled. – Bypass operation is automatically initiated in the event of a fault at the BT300 Drive. – The motor is connected to utility/line power. ● Interlock (electronic only) –...
WARNING Failure to disconnect input power may cause serious injury or death. When you connect input power to the Siemens BT300 Bypass, the motor terminals are energized even if the motor is not running. Do not make any connections with input power connected to the Siemens BT300 Bypass.
Apply power, and repeat Steps 13 through 15 to verify proper rotation again Place the DRIVE/OFF/BYPASS switch in the DRIVE position. Complete any other required wizards found in the Quick Setup (1) menu. Siemens Industry, Inc. BT300 Bypass Operator's Manual DPD01391 2016-08-05...
Page 14
Observe if the speed command can achieve the minimum and maximum speeds desired. If not, scale as required. Configure the Password and Access Level, if desired. This prevents unauthorized parameterization using the keypad. Siemens Industry, Inc. BT300 Bypass Operator's Manual DPD01391 2016-08-05...
Press the HAND/AUTO button on the drive. Select Drive, and press OK. Select Auto and press O. When Activate displays, press OK.. Complete any other required wizards found in the Quick Setup (1) menu. Complete any other application specific settings for the site as required. Siemens Industry, Inc. BT300 Bypass Operator's Manual DPD01391 2016-08-05...
Page 16
Observe if the speed command can achieve the minimum and maximum speeds desired. If not, scale as required. Configure the Password and Access Level, if desired. This prevents unauthorized parameterization using the keypad. Siemens Industry, Inc. BT300 Bypass Operator's Manual DPD01391 2016-08-05...
Quick Commissioning Procedure Quick Commissioning Procedure It is important to use the quick commissioning procedure as listed in the workflow. The wizards are in place to help minimize the startup time. Siemens Industry, Inc. BT300 Bypass Operator's Manual DPD01391 2016-08-05...
At the drive keypad, select: User Settings > Parameter Backup > Restore Factory Defa > Activate. The drive restarts, the Siemens splash screen displays, and the Startup Wizard automatically begins. See the Startup Wizard (P1.19) section for further details. Siemens Industry, Inc.
Once power is connected to the BT300 HVAC Drive, the Startup Wizard should run automatically. If it is not running, it can be activated in the Quick Setup (M1) menu or by completing Restore Factory Defaults (P6.5.1)
Page 20
0 = No 1 = Yes Bypass Wizard (P1.21) Enable parameter for the Bypass Wizard. This wizard can be activated during the Startup Wizard. The Startup Wizard is now complete. Siemens Industry, Inc. BT300 Bypass Operator's Manual DPD01391 2016-08-05...
OK to continue. The Bypass Wizard is now complete. Any site specific application programming should now be completed. Communications Configuration The communications configuration is documented in the Siemens BT300 HVAC Drive Operator’s Manual (DPD01809). Additional Configuration Depending upon the site and the sequence of operation desired, such as auto reset, flying start, skip frequencies, and switching frequency, additional configuration may be required.
At the drive keypad, press the Hand/Auto button. Use the Up and/or Down Arrow buttons to highlight Drive, and then press OK Use the Up and/or Down Arrow buttons to highlight Auto, and then press OK Siemens Industry, Inc. BT300 Bypass Operator's Manual DPD01391 2016-08-05...
At the drive keypad, press the Hand/Auto button. Use the Up and/or Down Arrow buttons to highlight Drive, and then press OK Use the Up and/or Down Arrow buttons to highlight Hand, and then press OK Siemens Industry, Inc. BT300 Bypass Operator's Manual DPD01391 2016-08-05...
In OFF mode, both the Bypass (M1) and the Output (M2) contactors are open to prevent power from getting to the motor. At the drive keypad, press the Hand/Auto button. Use the Up and/or Down Arrow buttons to highlight Off, and then press OK Siemens Industry, Inc. BT300 Bypass Operator's Manual DPD01391 2016-08-05...
The unit is now operating in the Bypass mode. Line supply power is directly supplied to the motor. No speed control is available in this mode. The display will return to the default display. Siemens Industry, Inc. BT300 Bypass Operator's Manual DPD01391 2016-08-05...
Disabled 1828 Enable parameter to the Remote Bypass feature. If enabled, when the unit is placed in Bypass mode, the M1 (Bypass) contactor opens/closes in accordance with Rem. Ctrl. Place (P3.2.1). Siemens Industry, Inc. BT300 Bypass Operator's Manual DPD01391 2016-08-05...
Application Features (Electronic Bypass Only) During the bypass wizard execution, if the unit is defined to have the Electronic Siemens BT300 Bypass, then the application features can be enabled. When the Electronic Bypass is enabled in the drive, digital inputs and relay outputs are configured automatically as listed below.
– If interlock logic is enabled and the essential services function is activated, the bypass contactor (M1) closes after ten seconds if the feedback signal is not received from the damper. Siemens Industry, Inc. BT300 Bypass Operator's Manual DPD01391 2016-08-05...
Default: 1.0s (as soon as possible). Auto Bypass If the Bypass Wizard was used to configure the Siemens BT300 Bypass and the Auto Bypass feature was enabled, then all required settings are automatically programmed. The Bypass Wizard can be executed again to disable the Auto Bypass feature, if desired.
Default: 1.0s (as soon as possible) Essential Services If the Bypass Wizard was used to configure the Siemens BT300 Bypass and the Essential Services feature was enabled, then all required settings will be automatically programmed. The Bypass Wizard can be executed again to disable the Essential Services feature, if desired.
Drive outputs to inhibit motor start until a safety condition (proofing sequence) is confirmed. Any call to start the motor from the BT300 Drive or bypass does not directly start the motor, but instead initiates the following interlock procedure: ●...
Some applications and motor characteristics may require up- sizing this protection. If this is required in the field, ensure that there is an appropriate match between the types of fuses and rating with the fuse holder. Siemens Industry, Inc. BT300 Bypass Operator's Manual DPD01391 2016-08-05...
General Bypass Problem Description Possible Cause Drive does not start on closing of the ● The Siemens BT300 Bypass is not in Drive - Auto Mode. run command. ● Drive output contactor is not closed. ● Remote contact is not closed. Replace with jumper to verify.
Page 43
- I/O Start) DI2 must be ON before 0 Vdc (Off) DI1 can be ON. TP15 TP15 0 Vdc 0 Vdc 0 Vdc 0 Vdc Vdc Common from drive standard I/O terminal 13. Siemens Industry, Inc. BT300 Bypass Operator's Manual DPD01391 2016-08-05...
Technical Information Power Ratings Power Ratings The following chart shows the BT300 HVAC Drive power ratings in accordance with frame sizes: Siemens Industry, Inc. BT300 Bypass Operator's Manual DPD01391 2016-08-05...
2 - Voltage (0/2 to 10 Vdc) or current (0/4 to 20 mA) Analog Inputs Resolution 0.1%; Accuracy ±1% 1 - Voltage (0/2 to 10 Vdc) or current (0/4 to 20 mA) Analog Outputs <500 W; Resolution 0.1%; Accuracy ±1% Siemens Industry, Inc. BT300 Bypass Operator's Manual DPD01391 2016-08-05...
Motor stall protection Motor underload protection Short-circuit protection of 10 Vdc and 24 Vdc reference voltages Accessories and Replacement Parts Table 8: BT300 HVAC Drive Accessories and Replacement Parts (Frame Size-Specific). Accessory Description Frame Size NEMA 1 to NEMA 12 Cover...
Page 49
NEMA 1 Cover BT300-CVR-2154-FS7 BT300-CVR-2154-FS8 NEMA 1 Gland Plate Table 9: Accessories. Part Number Description BT300-DIAGBD-BTC Conventional Bypass Diagnostic Board BT300-DIAGBD-BTE Electronic Bypass Diagnostic Board BTE-SW-KIT Electronic Bypass Override Switch Kit Siemens Industry, Inc. BT300 Bypass Operator's Manual DPD01391 2016-08-05...