Advertisement

Flux braking (P3.4.12)
Instead of DC braking, flux braking is a useful way to raise the braking capacity in cases where additional brake
resistors are not needed.
When braking is needed, the frequency is reduced and the flux in the motor is increased, which in turn increases
the motor's capability to brake. Unlike DC braking, the motor speed remains controlled during braking.
The flux braking can be set ON or OFF.

I/O Configuration (M3.5)

The I/O configuration is used to attach features/functions of the drive to the controlling I/O or control source. There
are four I/O configuration areas: Digital Inputs, Digital Outputs, Analog Inputs, and Analog Outputs.

Digital Inputs (M3.5.1)

The digital inputs are very flexible to use. Parameters are functions/features that are connected to the required
digital input terminals. The digital inputs are represented by the slot they exist on. For example, DigIN Slot A.2
means the second digital input on slot A (basic I/O). It is possible for the function/feature to be always disabled (or
enabled) by using the virtual slot0. For example, to leave a parameter as normally open all the time, it would be
programmed as DigIN Slot0.1. Likewise, to leave a parameter as normally closed all the time, it would be
programmed as DigIN Slot0.2.
It is also possible to connect the digital inputs to time channels which are also represented as terminals. For
example, to run the drive in reverse in accordance with the first time channel, it would be programmed as
TimeChannel.1.
Siemens Industry, Inc.
Building Technologies
Figure 17: Acceleration/Deceleration (S-shaped).
NOTE:
Flux braking converts the energy into heat at the motor, and should be used
intermittently to avoid motor damage.
NOTE:
The status of the digital inputs can be monitored in the multimonitor (M2.1) view, or in
the I/O and Hardware (M5) menu.
Siemens BT300 HVAC Drive
Chapter 4 - Parameters and Menu Structure
Parameters (M3)
53 | 180
DPD01809
2016-06-07