Quick Setup (M1)

The Quick Setup parameter group is a collection of parameters that are the most commonly used during installation
and commissioning. They are collected in the first parameter group so that they can be found quickly and easily.
However, they can be also be reached and edited in the actual parameter groups. Changing a parameter value in
the Quick Setup group also changes the value of this parameter in its actual group.
The Quick Setup parameters are presented in the following table:
Structure
Parameter
P1.1
Motor Nom Voltg
P1.2
Motor Nom Freq
P1.3
Motor Nom Speed
P1.4
Motor Nom Currnt
P1.5
Motor Cos Phi
P1.6
Motor Nom Power
P1.7
Current Limit
P1.8
Min Frequency
P1.9
Max Frequency
P1.10
I/O A Ctrl Ref
P1.11
Preset Freq 1
P1.12
Preset Freq 2
P1.13
Accel Time 1
P1.14
Decel Time 1
Siemens Industry, Inc.
Building Technologies
Table 4: Quick Setup Parameters.
Unit
ID
V
110
Defines nominal motor voltage from motor nameplate data.
Also see
Hz
111
Defines nominal motor frequency from motor nameplate data.
Also see
rpm
112
Defines nominal motor speed from motor nameplate data.
Also see
A
113
Defines nominal motor current from motor nameplate data.
Also see
120
Defines nominal motor Cos Phi (power factor) from motor nameplate data.
Also see
hp
116
Defines nominal motor power from motor nameplate data.
Also see
A
107
Defines maximum current limit for motor. Suggested to use Motor Nominal
Current (P1.4) multiplied by motor service factor from motor nameplate data.
Also see
Hz
101
Sets minimum motor frequency at which motor will run irrespective of
frequency setpoint.
Also see
Hz
102
Sets maximum motor frequency at which motor will run irrespective of
frequency setpoint.
Also see
117
Selects location of frequency setpoint source when in I/O A control. In the
following list of possible settings, the main setpoint is selected:
1= Preset Freq 0
2 = Keypad Reference
3 = Fieldbus
4 = AI1
5 = AI2
6 = AI1+AI2
7 = PID 1 Reference
8 = Motor Potentiometer
Also see
Hz
105
Used according to state of digital input defined for Preset Frequency
Selection 1 (P3.5.1.16). Decoding mode chosen with Preset Frequency Mode
(P3.3.10). Also see
Hz
106
Used according to state of digital inputs Preset Frequency Selection 2
(P3.5.1.17). Decoding mode chosen with Preset Frequency Mode (P3.3.10).
Also see
s
103
Time allowed for motor to accelerate from a standstill (0) up to Maximum
Frequency (P1.9).
This parameter can also be found in Menu Structure P3.4.2
s
104
Time allowed for motor to decelerate from Maximum Frequency (P1.9) to a
standstill (0). Also see
Siemens BT300 HVAC Drive
Chapter 4 - Parameters and Menu Structure
Description
Menu Structure P3.1.1.1
.
Menu Structure P3.1.1.2.
Menu Structure P3.1.1.3
.
Menu Structure P3.1.1.4
.
Menu Structure P3.1.1.5
.
Menu Structure P3.1.1.6.
Menu Structure P3.1.1.7.
Menu Structure P3.3.1.
Menu Structure P3.3.2.
Menu Structure P3.3.3.
Menu Structure P3.3.12
Menu Structure P3.3.13
.
Menu Structure P3.4.3
Quick Setup (M1)
.
.
DPD01809
2016-06-07
29 | 180