Control reference settings (M3.3)
The frequency reference source is programmable for all control places except the computer, which always takes the
reference from the PC tool.
Auto Control Place I/O A: The source of frequency reference can be selected with I/O Control Reference A
Selection (P3.3.3). The I/O B Reference Force (P3.5.1.6) will determine when the I/O Control Reference B is in use.
Auto Control Place I/O B: The source of frequency reference can be selected with I/O Control Reference B
Selection (P3.3.4). The I/O B Reference Force (P3.5.1.6) will determine when the I/O Control Reference B is in use.
Keypad (Hand) Control Place: The source of the frequency reference can be selected with Keypad Control
Reference Selection (P3.3.5). If set to a value of Keypad Reference; then the keypad buttons or Keypad Reference
(P3.3.6) can be used to set the frequency reference.
Fieldbus Control Place: The source of the frequency reference can be selected with Fieldbus Control Reference
Selection (P3.3.9).
Structure
Parameter
P3.3.1
Min Frequency
P3.3.2
Max Frequency
P3.3.3
I/O A Ctrl Ref
P3.3.4
I/O B Ctrl Ref
P3.3.5
Keypad Ctrl Ref
Siemens Industry, Inc.
Building Technologies
Table 26: Control Reference Settings.
Unit
Min
Hz
0
Parameter P3.3.2
Hz
Parameter
320
P3.3.1
PresetFreq0
Motor Pot Ref
PresetFreq0
Motor Pot Ref
PresetFreq0
Motor Pot Ref
Siemens BT300 HVAC Drive
Chapter 4 - Parameters and Menu Structure
Max
Default
0
101
60
102
AI1 + AI2
117
AI1
131
Keypad Ref
121
Parameters (M3)
ID
Description
Minimum allowed frequency
reference
Maximum allowed frequency
reference
Selects location of frequency setpoint
source when in I/O A control. In the
following list of possible settings, the
main setpoint is selected:
1 = Preset Freq 0
2 = Keypad Reference
3 = Fieldbus
4 = AI1
5 = AI2
6 = AI1+AI2
7 = PID 1 Reference
8 = Motor Potentiometer
Also see M1.10.
Selects location of frequency setpoint
source when in I/O B control. In the
following list of possible settings, the
main setpoint is selected:
1 = Preset Freq 0
2 = Keypad Reference
3 = Fieldbus
4 = AI1
5 = AI2
6 = AI1+AI2
7 = PID 1 Reference
8 = Motor Potentiometer
I/O B Ref Force (P3.5.1.6) is used to
determine when this reference is to
be followed.
Defines the location of Keyboard
Control Reference:
1 = Preset Freq 0
2 = Keypad Reference
3 = Fieldbus
4 = AI1
5 = AI2
6 = AI1+AI2
7 = PID 1 Reference
8 = Motor Potentiometer
47 | 180