Siemens bt300 Operator's Manual page 55

Hvac drive
Hide thumbs Also See for bt300:
Table of Contents

Advertisement

Structure
Parameter
P3.5.1.13
Run Interlock 2
P3.5.1.14
PreHeat ON
P3.5.1.15
Preset Freq Sel0
P3.5.1.16
Preset Freq Sel1
P3.5.1.17
Preset Freq Sel2
P3.5.1.18
Timer 1
P3.5.1.19
Timer 2
P3.5.1.20
Timer 3
P3.5.1.21
Disable Timer Funct.
P3.5.1.22
PID1 Boost SP
P3.5.1.23
PID1 Select SP
P3.5.1.24
PID2 Start Signal
P3.5.1.25
PID2 Select SP
P3.5.1.26
Interlock 1
P3.5.1.27
Interlock 2
P3.5.1.28
Interlock 3
P3.5.1.29
Interlock 4
Siemens Industry, Inc.
Building Technologies
Default
ID
DigIN Slot0.2
1042
DigIN Slot0.1
1044
DigIN SlotA.4
419
DigIN SlotA.5
420
DigIN Slot0.1
421
DigIN Slot0.1
447
DigIN Slot0.1
448
DigIN Slot0.1
449
DigIN Slot0.1
1499
DigIN Slot0.1
1047
DigIN Slot0.1
1046
DigIN Slot0.2
1049
DigIN Slot0.1
1048
DigIN Slot0.1
426
DigIN Slot0.1
427
DigIN Slot0.1
428
DigIN Slot0.1
429
Siemens BT300 HVAC Drive
Chapter 4 - Parameters and Menu Structure
Description
Defines the input monitored for proof of the interlock application
when Mot. Interlock Start (P3.2.11) is enabled.
The Drive cannot be started if any of the interlocks are open. This
function can be used for a damper interlock, preventing the Drive
from starting with the damper closed.
Used when Preheat Function (P3.1.2.5) is set to 2
0 = No action
1 = Used motor preheat DC current in Stop state
Defines the location for the binary selector 0 used with
PresetFreqMode (P3.3.10), and Preset Freq 1 (P3.3.12), through
Preset Freq 7 (P3.3.18).
Defines the location for the binary selector 0 used with
PresetFreqMode (P3.3.10), and Preset Freq 1 (P3.3.12), through
Preset Freq 7 (P3.3.18).
Defines the location for the binary selector 0 used with
PresetFreqMode (P3.3.10), and Preset Freq 1 (P3.3.12), through
Preset Freq 7 (P3.3.18).
Defines the location to the rising edge to start timer 1 as
programmed in Timer Functions (P3.11) menu structure.
Defines the location to the rising edge to start timer 2 as
programmed in Timer Functions (P3.11) menu structure.
Defines the location to the rising edge to start timer 3 as
programmed in Timer Functions (P3.11) menu structure.
Enable parameter for all timer functions including Intervals 1-5 and
Timer 1-3 (programmable in Timer Functions (P3.11) menu
structure).
Contact closure = Timer functions and reset timers disabled
Open Contact = Timer functions and reset timers enabled
Defines the location for applying boost to PID1 setpoint.
Contact closure = Boost
Open Contact = No Boost
Defines the location to determine which setpoint is to be used with
PID1.
Open Contact = Setpoint 1
Contact Closure = Setpoint 2
Parameter will have no effect if PID2 controller is not enabled in the
basic menu for PID2.
Open Contact = PID2 in stop mode
Contact Closure = PID2 regulating
Defines the location to determine which setpoint is to be used with
PID2.
Open Contact = Setpoint 1
Contact Closure = Setpoint 2
Defines the location for the interlock feedback for motor 1 when
using the multi-pump feature.
Defines the location for the interlock feedback for motor 2 when
using the multi-pump feature.
Defines the location for the interlock feedback for motor 3 when
using the multi-pump feature.
Defines the location for the interlock feedback for motor 4 when
using the multi-pump feature.
Parameters (M3)
55 | 180
DPD01809
2016-06-07