Chapter 4 - Parameters and Menu Structure
Parameters (M3)
Structure
Parameter
P3.5.1.30
Interlock 5
P3.5.1.31
MotPot UP
P3.5.1.32
MotPot Down
P3.5.1.33
Acc/Dec Time Sel
P3.5.1.34
Fieldbus Ctrl
P3.5.1.39
FireMode Activ.Open
P3.5.1.40
FireMode Activ.Close
P3.5.1.41
FireMode Reverse
P3.5.1.42
Keypad CTRL
P3.5.1.43
Reset kWh Counter
P3.5.1.44
Remote Safety 1*
P3.5.1.45
Remote Safety 2*
P3.5.1.46
Remote Safety 3*
P3.5.1.47
Remote Safety 4*
P3.5.1.48
Remote Safety 5*
P3.5.1.49
Remote Safety 6*
P3.5.1.50
Remote Safety 7*
P3.5.1.51
Remote Safety 8*
P3.5.1.52
Essential Services*
P3.5.1.53
Overload
(Accessible when
Bypass (P3.17.4) =
Electronic or
Conventional
56 | 180
Siemens Industry, Inc.
Building Technologies
Default
ID
DigIN Slot0.1
430
DigIN Slot0.1
418
DigIN Slot0.1
417
DigIN Slot0.1
408
DigIN Slot0.1
411
DigIN Slot0.2
1569
DigIN Slot0.1
1619
DigIN Slot0.1
1618
DigIN Slot0.1
410
DigIN Slot0.1
1053
DigIN SlotA.2
1814
DigIN SlotA.3
1815
DigIN Slot0.2
1819
DigIN Slot0.2
1820
DigIN Slot0.2
1821
DigIN Slot0.2
1822
DigIN Slot0.2
1823
DigIN Slot0.2
1824
DigIN Slot0.1
1827
DigIN SlotA.5
1825
*Accessible only when Bypass (P3.17.4) is set to a value of Electronic.
Siemens BT300 HVAC Drive
Description
Defines the location for the interlock feedback for motor 5 when
using the multi-pump feature.
Defines the location for the motor potentiometer reference that will
be used to increase the speed.
Contact closure = increase speed setpoint.
Defines the location for the motor potentiometer reference that will
be used to decrease the speed
Contact closure = decrease speed setpoint
Defines the location for accel/decel time selection.
Open Contact = Ramp 1 shape (P3.4.1), Accel1 (P3.4.2), and
Decel1 (P3.4.3) to be followed
Contact Closure = Ramp 2 shape (P3.4.4), Accel2 (P3.4.5), and
Decel 2 (P3.4.6) to be followed
Defines the location to force control place to fieldbus.
Open Contact = I/O Control
Contact closure = Fieldbus Control
Defines location of fire mode activation on contact opening.
Open Contact = Fire Mode Active
Contact Closure = No Action
Also see Menu Structure P3.16.2.
Defines location of fire mode activation on contact closing.
Open Contact = No Action
Contact Closure = Fire Mode Active
Also see Menu Structure P3.16.3.
Defines location of the reverse command when fire mode is active
as defined by FireMode Activ.Open (P3.16.2) or FireMode
Activ.Close (P3.16.3).
Open Contact = Forward
Contact Closure = Reverse
NOTE: This function has no effect in normal mode of operation.
Also see Menu Structure P3.16.6.
Defines the location monitored to force the Control Place to Keypad.
Defines the location of the kWh trip counter reset.
Defines the location of the remote safety.
Defines the location of the remote safety.
Defines the location of the remote safety.
Defines the location of the remote safety.
Defines the location of the remote safety.
Defines the location of the remote safety.
Defines the location of the remote safety.
Defines the location of the remote safety.
Defines the location of the essential service activation signal.
NOTE: Requires EssentServEnable (P3.18.5) to be enabled to take
effect.
Defines the location of the bypass overload relay.
NOTE: Is it not recommended to change this value. The overload
relay is factory wired to digital input 5 on all Conventional and
Electronic Bypass options.
DPD01809