Structure
Parameter
P3.9.11
MotorStall Flt
P3.9.12
Stall Current
P3.9.13
Stall Time Limit
P3.9.14
Stall Freq.Limit
P3.9.15
Underload Flt
P3.9.16
UL FieldweakLoad
P3.9.17
UL ZeroFreq.Load
P3.9.18
UL Time Limit
P3.9.19
FieldbusComm Flt
P3.9.20
SlotComm Flt
P3.9.21
Thermistor Fault
Siemens Industry, Inc.
Building Technologies
Unit
Min
Max
0
3
A
0
2*IH
s
1
120
Hz
1
Parameter
P1.9 or
P3.3.2
0
3
%
10
150
%
5
150
s
2
600
No Action
4
No Action
Fault, Coast Fault
No Action
Fault, Coast No Action
Siemens BT300 HVAC Drive
Chapter 4 - Parameters and Menu Structure
Default
ID
0
709
Defines the response to a motor stall.
Response settings are as follows:
0 = No Action
1 = Alarm
2 = Fault
3 = Fault
IH
710
For a stall stage to occur, the current must
have exceeded this limit.
15
711
This is the maximum time allowed for a
stall stage.
25
712
For a stall stage to occur, the output
frequency must have remained below this
limit for a certain time.
0
713
Defines the response to an underload.
Response settings are as follows:
0 = No Action
1 = Alarm
2 = Fault
3 = Fault
50
714
This parameter gives the value for the min
torque allowed when the output frequency
is above the field weakening point.
10
715
This parameter gives the value for the min
torque allowed with zero frequency.
20
716
This is the maximum time allowed for an
underload state to exist.
Fault
733
Defines the response to a fieldbus
communications signal loss. Response
settings are as follows:
0 = No Action
1 = Alarm
2 = Alarm and run to PresetAlarmFreq
(P3.3.19)
3 = Fault
4 = Fault
734
Defines the response to an option card slot
communications failure. Response settings
are as follows:
0 = No Action
1 = Alarm
2 = Fault
3 = Fault
732
Defines the response to a thermistor
failure. Response settings are as follows:
0 = No Action
1 = Alarm
2 = Fault
3 = Fault
NOTE
Fault (according to stop mode) if a BT300-
OPT-B4-V option card is installed.
Parameters (M3)
Description
(stop according to stop mode)
(stop by coasting)
(stop according to stop mode)
(stop by coasting)
(stop according to stop mode)
(stop by coasting)
(stop according to stop mode)
(stop by coasting)
(stop according to stop mode)
(stop by coasting)
: It is recommend to set to a value of
73 | 180
DPD01809