Dead band (P3.12.1.9)
Dead band delay (P3.12.1.10)
Sleep frequency limit 1 (P3.12.2.7), Sleep delay 1 (P3.12.2.8), and Wake-up level 1 (P3.12.2.9)
This function puts the drive into sleep mode if the frequency stays below the sleep limit for a longer period than
that set with the Sleep Delay (P3.12.2.8). This means that the start command remains on, but the run request is
turned off. When the actual value goes below or above the wake-up level depending on the set acting mode, the
drive will activate the run request again, if the start command is still on.
Siemens Industry, Inc.
Building Technologies
Figure 25: Dead band.
Siemens BT300 HVAC Drive
Chapter 4 - Parameters and Menu Structure
Reference
Output locked
Parameters (M3)
Actual value
11105.emf
93 | 180
DPD01809
2016-06-07