Structure
Parameter
P3.5.2.21
AI4 Signal Range
P3.5.2.22
AI4 Cutom Min
P3.5.2.23
AI4 Custom Max
P3.5.2.24
AI4 Signal Inv
P3.5.2.25
AI5 Signal Sel
P3.5.2.26
AI5 Filter Time
P3.5.2.27
AI5 Signal Range
P3.5.2.28
AI5 Cutom Min
P3.5.2.29
AI5 Custom Max
P3.5.2.30
AI5 Signal Inv
P3.5.2.31
AI6 Signal Sel
Siemens Industry, Inc.
Building Technologies
Unit
Min
Max
0-10V/
2-10V/
0-20mA
4-20mA
%
-160
160
&
-160
160
Normal
Inverted
s
0
300
0-10V/
2-10V/
0-20 mA
4-20 mA
%
-160
160
&
-160
160
Normal
Inverted
Siemens BT300 HVAC Drive
Chapter 4 - Parameters and Menu Structure
Default
ID
0-10V/
154
Defines the signal range for the
0-20mA
analog input defined by AI4 Signal
Sel (P3.5.2.19). Ranges are as
follows:
0 = 0 to 10 Vdc/0 to 20 mA
1 = 2 to 10 Vdc/4 to 20 mA
NOTE: This setting can be
bypassed by using AI4 Custom Min
(P3.5.2.22) and AI4 Custom Max
(P3.5.2.23).
0
155
Defines the custom minimum to be
used for bypassing the AI4 Signal
Range (P3.5.2.21).
100
156
Defines the custom maximum to be
used for bypassing the AI4 Signal
Range (P3.5.2.21).
Normal
162
Defines the operation of the analog
input 4 signal as follows:
Normal = 0V or 0 mA = 0%, 10V or
20 mA = 100%
Inverted = 0V or 0 mA = 100%, 10V
or 20 mA = 0%
AnIN Slot0.1 188
Defines the location of the signal to
be used as analog input 5.
1
189
Defines the time it takes to reach
63% of a step change in the analog
input signal defined by AI5 Signal
Sel (P3.5.2.25).
0-10V/
190
Defines the signal range for the
0-20 mA
analog input defined by AI5 Signal
Sel (P3.5.2.25). Ranges are as
follows:
0 = 0 to 10 Vdc/0 to 20 mA
1 = 2 to 10 Vdc/4 to 20 mA
NOTE: This setting can be
bypassed by using AI5 Custom Min
(P3.5.2.28) and AI5 Custom Max
(P3.5.2.29).
0
191
Defines the custom minimum to be
used for bypassing the AI5 Signal
Range (P3.5.2.27).
100
192
Defines the custom maximum to be
used for bypassing the AI5 Signal
Range (P3.5.2.27).
Normal
198
Defines the operation of the analog
input 5 signal as follows:
Normal = 0Vor 0 mA = 0%, 10V or
20 mA = 100%
Inverted = 0V or 0 mA = 100%, 10V
or 20 mA = 0%
AnIN Slot0.1 199
Defines the location of the signal to
be used as analog input 6.
Parameters (M3)
Description
59 | 180
DPD01809
2016-06-07