P1 Fln (M5.8.3) - Siemens bt300 Operator's Manual

Hvac drive
Hide thumbs Also See for bt300:
Table of Contents

Advertisement

5. Select: Main Menu > I/O and Hardware (M5) > RS-485 (M5.8) > BACnet MSTP (M5.8.3) > Parameters
(M5.8.3.1) > MAC Address (P5.8.3.1.2) > Edit.
6. Enter the desired network device address and press the
7. Select: Main Menu > I/O and Hardware (M5) > RS-485 (M5.8) > BACnet MSTP (M5.8.3) > Parameters
(M5.8.3.1) > Instance Number (P5.8.3.1.3) > Edit.
8. Enter the desired instance number and press the
router is on the network.)
9. Select: Main Menu > I/O and Hardware (M5) > RS-485 (M5.8) > BACnet MSTP (M5.8.3) > Parameters
(M5.8.3.1) > Comm. Timeout (P5.8.3.1.5) > Edit.
10. Enter the desired time for drive to monitor for a communications loss and press the
disables this monitoring.
For commanding Start/Stop and Speed Reference using the BACnet MS/TP protocol, complete the following steps:
1. Complete all settings required for Monitoring as listed above.
2. Set Ctrl. Place Auto (P3.2.1) to a value of FieldbusCTRL.
For commanding Start/Stop through the BACnet MS/TP protocol and Speed Reference through an Analog Input,
complete the following changes:
1. Complete all settings required for Monitoring as listed above.
2. Set Ctrl. Place Auto (P3.2.1) to a value of FieldbusCTRL.
3. Set FieldbusCtrl Ref (P3.3.9) to a value of AI1 or AI2 (depending upon which AI is in use).
For commanding Start/Stop through a Digital Input and Speed Reference through the BACnet MS/TP protocol,
complete the following steps:
1. Complete all settings required for Monitoring as listed above.
2. Set Ctrl. Place Auto (P3.2.1) to a value of I/O Control.
3. Set I/O A Ctrl Ref (P3.3.3) to a value of Fieldbus.

P1 FLN (M5.8.3)

The Siemens P1 FLN fieldbus communications protocol is used by Siemens and others to connect terminal unit
controllers to supervisory controllers. It is open to any manufacturer and widely used in the HVAC controls industry.
The physical characteristics of the P1 FLN bus is an RS-485 three-wire, with a maximum of 96 devices over a
4,000 foot (1219 m) distance, running at 4800 bps. The RS-485 interface is a half-duplex system. The transfer
cable is supported as a Shielded Twisted Pair, type Belden 98410 or similar. However, on variable speed drives,
the third wire (shield) is not terminated to the drive itself.
Logically, the P1 FLN is a master-slave protocol, with the supervisory controller being the master. Device points
are partitioned into common HVAC control types, such as analog input, analog output, digital input, and digital
output. P1 FLN messaging supports the reading, writing and overriding of these points.
The P1 FLN fieldbus protocol supports the following point types:
Logical Digital Input (LDI) – a two-state input for reading status.
Logical Digital Output (LDO) – a two-state output for commanding.
Siemens Industry, Inc.
Building Technologies
Chapter 4 - Parameters and Menu Structure
button.
button. (Used when a BACnet MS/TP to BACnet IP
Siemens BT300 HVAC Drive
I/O and Hardware (M5)
button. A value of 0
131 | 180
DPD01809
2016-06-07