Siemens bt300 Operator's Manual page 145

Hvac drive
Hide thumbs Also See for bt300:
Table of Contents

Advertisement

ID Map
Using the ID map, you can read consecutive memory blocks that contain parameters whose IDs are not in a
consecutive order. The address range 10501 through 10530 is called
which you can write your parameter IDs in any order. The address range 10601 through 10630 is called
Read/Write
, and includes values for parameters written in the ID map. As soon as one ID number has been written
in the map cell 10501, the corresponding parameter value can be read and written in the address 10601, and so
on.
Once the IDMap address range has been initialized with any parameter ID number, the parameter value can be
read and written in the IDMap Read/Write address range address IDMap address + 100.
If the IDMap table has not been initialized, all fields show the index 0. If it has been initialized, the parameter IDs
included in it are stored in the flash memory of the OPT-CI board.
Siemens Industry, Inc.
Building Technologies
Table 119: ID Map Initialization.
Data
Address
10501
700
10502
702
10503
707
10504
704
9328.emf
Table 120: Parameter Values in 16-bit IDMap Read/Write Registers.
Address
410601
Data included in parameter ID700
410602
Data included in parameter ID702
410603
Data included in parameter ID707
410604
Data included in parameter ID704
Siemens BT300 HVAC Drive
Chapter 4 - Parameters and Menu Structure
I/O and Hardware (M5)
IDMap
, and includes an address map in
Parameter ID's
ID
699
700
701
702
703
704
705
706
707
708
Data
IDMap
145 | 180
DPD01809
2016-06-07