Chapter 4 - Parameters and Menu Structure
I/O and Hardware (M5)
Structure
Parameter
M5.8.3.2.8
Slave Dev. Failure
M5.8.3.2.9
Last Fault
Response
M5.8.3.2.10
Control Word
M5.8.3.2.11
Status Word
Modbus RTU Parameters
Slave address (P5.8.3.1.1)
Each slave must have a unique address (from 1 through 247) so that it can be addressed independently from other
nodes.
Baud rate (P5.8.3.1.2)
Select the communication speed for the network. The default value is 9600 baud.
Parity type (P5.8.3.1.3)
You can select the parity type for the network.
138 | 180
Siemens Industry, Inc.
Building Technologies
Unit
Min
Max
Siemens BT300 HVAC Drive
Default
ID
2388
Displays if the server (slave) has
detected a parity error in the
memory when reading a record.
2389
Displays the last fault response as
fault code as follows:
0 = None (No fault detected since
last power-up)
1 = Connection Timeout (time
defined in Comm. Timeout
(M5.8.3.1.5) has expired and token
has not be received)
2390
Displays the control word received
from the fieldbus. Based on 32 bits
as described below:
B0 = Start/Stop (0 = Stop; 1 = Start)
B1 = Direction (0 = Forward; 1 =
Reverse)
B2 = Fault Reset (0 = No action; 1 =
Reset faults)
B3 - B31 = Not used
2391
Displays the status word sent to the
fieldbus. Based on 32 bits as
described below:
B0 = Ready (0 = Not Ready; 1 =
Ready)
B1 = Run (0 = Stopped; 1 =
Running)
B2 = Direction (0 = Forward; 1 =
Reverse)
B3 = Fault (0 = No faulted; 1 =
Faulted)
B4 = Alarm (0 = No alarm; 1 =
Alarm)
B5 = At Reference (0 = False; 1 =
True)
B6 = Zero Speed (0 = False; 1 =
True)