Digital Outputs (M3.5.3) - Siemens bt300 Operator's Manual

Hvac drive
Hide thumbs Also See for bt300:
Table of Contents

Advertisement

Chapter 4 - Parameters and Menu Structure
Parameters (M3)
Structure
Parameter
P3.5.2.32
AI6 Filter Time
P3.5.2.33
AI6 Signal Range
P3.5.2.34
AI6 Cutom Min
P3.5.2.35
AI6 Custom Max
P3.5.2.36
AI6 Signal Inv

Digital Outputs (M3.5.3)

The digital/relay outputs are very flexible to use. Parameters are functions/features that are connected to the
required digital/relay output terminals. The digital outputs are configured by the slot they exist on. If no expansion
board exists, then the option does not populate with data.
Digital outputs, slot B (Basic)
Structure
Parameter
P3.5.3.2.1
RO1 Function
P3.5.3.2.2
RO1 ON Delay
P3.5.3.2.3
RO1 OFF Delay
60 | 180
Siemens Industry, Inc.
Building Technologies
Unit
Min
s
0
300
0-10V/
2-10V/
0-20mA
4-20 mA
%
-160
160
&
-160
160
Normal
Inverted
NOTE:
The status of the Digital/Relay Outputs can be monitored in the Multimonitor (M2.1)
view, or in the I/O and Hardware (M5) menu.
Table 33: Digital Outputs, Slot B.
Unit
Min
None
Remote Start Run
s
0
320
s
0
320
Siemens BT300 HVAC Drive
Max
Default
ID
1
200
0-10V/
201
0-20 mA
0
203
100
204
Normal
209
Max
Default
ID
11001
0
11002
0
11003
Description
Defines the time it takes to reach
63% of a step change in the analog
input signal defined by AI6 Signal
Sel (P3.5.2.31).
Defines the signal range for the
analog input defined by AI6 Signal
Sel (P3.5.2.31). Ranges are as
follows:
0 = 0 to 10 Vdc/0 to 20 mA
1 = 2 to 10 Vdc/4 to 20 mA
NOTE: This setting can be
bypassed by using AI6 Custom Min
(P3.5.2.34) and AI6 Custom Max
(P3.5.2.35).
Defines the custom minimum to be
used for bypassing the AI6 Signal
Range (P3.5.2.33).
Defines the custom maximum to be
used for bypassing the AI6 Signal
Range (P3.5.2.33).
Defines the operation of the analog
input 6 signal as follows:
Normal = 0V or 0 mA = 0%, 10V or
20 mA = 100%
Inverted = 0V or 0 mA = 100%, 10V
or 20 mA = 0%
Description
Basic RO Functions Table
See
Defines the amount of time that will
pass before the relay output will
energize (ON) after trigger of the
RO1 Function (P3.5.3.2.1).
Defines the amount of time that will
pass before the relay output will de-
energize (OFF) after trigger of the
RO1 Function (P3.5.3.2.1).
DPD01809
2016-06-07
.