Step
Parameter/Question
2
Bypass Delay (P3.18.1) Time
3
Essential Services* (P3.18.5)
If Enabled is selected for Essential Services, Step 4 displays. Otherwise, the wizard jumps directly to Step 5.
Step
Parameter/Question
4
Essential Services Activation (P3.5.1.52)
5
Remote Bypass* (P3.18.6)
If Enabled is selected for Remote Bypass, Step 6 displays. Otherwise, the wizard jumps directly to Step 7.
Step
Parameter/Question
6
Command Source (P3.5.1.1)
7
Interlock* (P3.2.11)
If Enabled is selected for Interlock, Step 8 displays. Otherwise, the wizard jumps directly to Step 9.
Step
Parameter/Question
8
Interlock Delay (P3.2.12)
9
Auto Bypass* (P3.18.2)
If Enabled is selected for Auto Bypass, Step 10 displays. Otherwise, the wizard jumps directly to Step 11.
Step
Parameter/Question
10
Auto Bypass Delay (P3.18.4)
11
Fault Selection (P3.18.3)
* Feature of the Electronic Bypass Option. For more details
The Bypass Wizard is now complete. The following message displays: Bypass Wizard is now complete.
Press OK to continue.
If Disabled is selected, no changes occur and the wizard completes The following message displays: Bypass
Wizard is now complete. Press OK to continue.
For more information on the bypass options, see the
Instructions
(DPD01375) and the
Siemens Industry, Inc.
Building Technologies
Defines the amount of time between the unit being
placed into Bypass mode and the M1 contactor closing.
Range: 1 to 30 s
Enabled
Disabled
DigIN SlotA.6
Enabled
Disabled
Fieldbus CTRL
I/O Control
Enabled
Disabled
Range: 0 to 120 s
Enabled
Disabled
Range: 0 to 30 s
Select faults to enable auto Bypass:
Any Fault
Undervoltage
Overvoltage
Overcurrent
AI Low
Unit Temperature
Motor Overtemp
External Fault
Underload Fault
BT300 Variable Frequency Drive Bypass Installation
BT300 Variable Frequency Drive Bypass Operator's Manual
Siemens BT300 HVAC Drive
Chapter 3 - Start-up Information
Settings
Settings
Settings
Settings
Settings
,
BT300 Bypass Operator
see
Wizards
s Manual
'
(DPD01391)
(DPD01391).
27 | 180
DPD01809
2016-06-07