Chapter 4 - Parameters and Menu Structure
I/O and Hardware (M5)
Example of 32-Bit IDMap
Operation Day Counter
Resettable Operation Day Counter
Reset the counter by writing 1 for Parameter ID2311.
Energy Counter
The last number of the Format field indicates the decimal point place in the Energy field. If the number is bigger
than 0, move the decimal point to the left by the number indicated. For example, Energy = 1200, Format = 52. Unit
= 1. Energy = 12.00 kWh.
146 | 180
Siemens Industry, Inc.
Building Technologies
Table 121: Example of Parameter Values in 32-bit IDMap Read/Write Registers.
Address
410701
Data High, parameter ID700
410702
Data Low, parameter ID700
410703
Data High, parameter ID702
410704
Data Low, parameter ID702
Table 122: Operation Day Counter.
Address
Register
40001
440001
40002
440002
40003
440003
40004
440004
40005
440005
Table 123: Resettable Operation Day Counter.
Address
Register
40101
440101
40102
440102
40103
440103
40104
440104
40105
440105
Siemens BT300 HVAC Drive
Data
Purpose
Years
Days
Hours
Minutes
Seconds
Purpose
Years
Days
Hours
Minutes
Seconds
DPD01809
2016-06-07