Chapter 5 - Fault Tracing
Fault Codes
66
1066
Thermistor fault
69
1310
Fieldbus
mapping error
1311
1312
80
1080
Remote Safety 1*
1180
Remote Safety 2*
1280
Remote Safety 3*
1380
Remote Safety 4*
1480
Remote Safety 5*
1580
Remote Safety 6*
1680
Remote Safety 7*
1780
Remote Safety 8*
81
1081
Overload**
82
1082
Bypass Not Possible* OPT-B5 relay board is missing. Bypass is not
83
1083
Essential Services*
84
1084
Run Interlock Proof
101
1101
Process
supervision fault
(PID1)
105
1105
Process
supervision fault
(PID2)
170 | 180
Siemens Industry, Inc.
Building Technologies
The thermistor input has detected an increase of
motor temperature.
Non-existing ID number is used for mapping
values to Fieldbus Process Data Out.
Not possible to convert one or more values for
Fieldbus Process Data Out.
Overflow when mapping and converting values for
Fieldbus Process Data Out (16-bit).
Digital input
Overload Relay has triggered the fault.
possible without the relay board.
Essential Services activated through digital input.
The run interlock proof hass failed to be provided
within the time allotted in Run Interlock Proof
(P3.2.13).
PID controller: Feedback value outside of
supervision limits (and the delay if set).
PID controller: Feedback value outside of
supervision limits (and delay, if set).
* Faults only possible with an Electronic Bypass Option.
** Faults only possible with a Bypass Option.
Siemens BT300 HVAC Drive
Check motor cooling and load.
Check thermistor connection
(If thermistor input is not in use it must be
short circuited)
Check parameters in Fieldbus Data Mapping
menu.
The value being mapped may be of an
undefined type. Check parameters in the
Fieldbus Data Mapping menu.
Verify the status of the digital input as defined
by Remote Safety 1 (P3.5.1.44).
Verify the status of the digital input as defined
by Remote Safety 2 (P3.5.1.45).
Verify the status of the digital input as defined
by Remote Safety 3 (P3.5.1.46).
Verify the status of the digital input as defined
by Remote Safety 4 (P3.5.1.47).
Verify the status of the digital input as defined
by Remote Safety 5 (P3.5.1.48).
Verify the status of the digital input as defined
by Remote Safety 6 (P3.5.1.49).
Verify the status of the digital input as defined
by Remote Safety 7 (P3.5.1.50).
Verify the status of the digital input as defined
by Remote Safety 8 (P3.5.1.51).
Reset the overload relay in the bypass
cabinet.
Verify connection of the OPT-B5 option board
in Slot C, D, or E. Install if required when
power is not applied to the drive.
Verify the status of the digital input as defined
by Essential Services (P3.5.1.52). Verify the
status of the EssentServEnable (P3.18.5).
Verify proper operation of the proof feedback
source.
DPD01809
2016-06-07