Chapter 4 - Parameters and Menu Structure
Parameters (M3)
The digital inputs settings are presented in the following table:
Structure
Parameter
P3.5.1.1
Ctrl Signal 1 A
(Start Forward)
P3.5.1.2
Ctrl Signal 2 A
(Start Reverse)
P3.5.1.3
Ctrl Signal 1 B
(Start Forward)
P3.5.1.4
Ctrl Signal 2 B
(Start Reverse)
P3.5.1.5
I/O B Ctrl Force
P3.5.1.6
I/O B Ref Force
P3.5.1.7
Ext Fault Close
P3.5.1.8
Ext Fault Open
P3.5.1.9
Fault Reset Close
P3.5.1.10
Fault Reset Open
P3.5.1.11
Run Enable
P3.5.1.12
Run Interlock 1
54 | 180
Siemens Industry, Inc.
Building Technologies
Table 31: Digital Inputs Settings.
Default
ID
DigIN SlotA.1
403
DigIN SlotA.2
404
DigIN Slot0.1
423
DigIN Slot0.1
424
DigIN Slot0.1
425
DigIN Slot0.1
343
DigIN SlotA.3
405
DigIN Slot0.2
406
DigIN SlotA.6
414
DigIN Slot0.1
213
DigIN Slot0.2
407
DigIN Slot0.2
1041
Siemens BT300 HVAC Drive
Description
Defines the location for selection of Control Signal 1 A as defined by
I/O A Logic (P3.2.6) [Start Forward]
Possible settings are as follows:
TimeChannel.#
DigIN Slot0.#
DigIN SlotA.#
DigIN SlotC.#
DigIN SlotD.#
DigIN SlotE.#
Where # is the channel number or occurrence number.
NOTE:
Slot C, D, and E available if option cards are installed and
contain Digital Input type objects.
Defines the location for selection of Control Signal 2 A as defined by
I/O A Logic (P3.2.6) [Start Reverse].
Possible settings are the same as Ctrl Signal 1 A (P3.5.1.1).
Defines the location for selection of Control Signal 1 B as defined by
I/O B Logic (P3.2.7) [Start Forward].
Possible settings are the same as Ctrl Signal 1 A (P3.5.1.1).
Defines the location for selection of Control Signal 2 B as defined by
I/O B Logic (P3.2.7) [Start Reverse].
Possible settings are the same as Ctrl Signal 1 A (P3.5.1.1).
Defines the location to determine when I/O B Logic (P3.2.7) should
be followed.
Open Contact = I/O A Logic (P3.2.6) is followed.
Contact Closure = I/O B Logic (P3.2.7) is followed.
Defines the location to determine when I/O B Ctrl Ref (P3.3.4)
should be followed.
Open Contact = I/O A Ctrl Ref (P3.3.3) is followed.
Contact Closure = I/O B Ctrl Ref (P3.3.4) is followed.
Defines the location to monitor to generate response to External
Fault (P3.9.2) on contact closure.
Open Contact = OK
Contact Closure = External Fault Active
Defines the location to monitor to generate response to External
Fault (P3.9.2) on contact open.
Open Contact = External Fault Active
Contact Closure = OK
Defines the location of fault reset on contact closure (rising edge).
Contact Closure = Reset
Defines the location of fault reset on open contact (falling edge).
Open Contact = Reset
Defines the location of the run enable.
Open Contact = Disabled = NOT READY
Contact Closure = Enabled = READY
The VFD is stopped according to the Stop Function (P3.2.5).
NOTE: When fieldbus is used, refer to FB Run Enable (P3.6.9).
Defines the input monitored for proof of the interlock application
when Mot. Interlock Start (P3.2.11) is enabled.
The drive cannot be started if any of the interlocks are open. This
function can be used for a damper interlock, preventing the drive
from starting with the damper closed.