Chapter 3 - Start-up Information

Wizards

Wizards
Wizards are available in the Quick Setup (M1) menu. The wizards assist you with various start-up and
commissioning functions. There are five wizards available in the BT300 HVAC Drive that prompt for essential
information needed for the following:
Start-up Wizard - Easy commissioning of the drive.
PID Mini-Wizard - Proper configuration of internal PID Loop Controller 1.
Multi-Pump Wizard - Proper configuration of the Multi-pump application.
Fire-Mode Wizard - Proper configuration of the Fire-mode.
Bypass Wizard - Proper configuration of the bypass options (if connected).

Startup Wizard (P1.19)

The Startup Wizard prompts you for the essential information needed by the drive so that it can start controlling the
output as desired. Once power is connected to the BT300 HVAC Drive, the Startup Wizard should run
automatically. If it is not running, it can be activated in the Quick Setup (M1) menu or by completing Restore
Factory Defaults (P6.5.1)
The following steps are required to successfully complete the Startup Wizard:
Step
Parameter/Question
1
Language Selections (P6.1)
2
Daylight Saving (P5.5.5)
3
Time (P5.5.2)
4
Year (P5.5.4)
5
Date (P5.5.3)
6
Startup Wizard?
If the option Yes is selected for Startup Wizard (recommended), you will be prompted for the following values:
Step
Parameter/Question
7
Fan or Pump
(Application Type)
8
Motor Nom Voltg (P3.1.1.1)
9
Motor Nom Freq (P3.1.1.2)
22 | 180
Siemens Industry, Inc.
Building Technologies
Select the icon for the language you want applied to the keypad. This
varies depending upon the language package installed.
Select the Daylight Saving Rule
1 = Off
2 = EU
3 = US
4 = Russia
Specify the current time of day in the following format: hh:mm:ss where
h = hour, m = minute, s = seconds.
Specify the current year in the following format: yyyy where
yyyy = 4-digit year.
Specify the current date in the following format: dd.mm where
dd = 2-digit day, mm = 2-digit month.
Specify if the Startup Wizard should be activated: Yes, No
Pump
Automatically sets the following:
Accel Time 1 (P1.13) = 30
Decel Time 1 (P1.14) = 30
Start Function (P3.2.4) = Ramping
Stop Function (P3.2.5) = Ramping
Fan
Automatically sets the following:
Accel Time 1 (P1.13) = 120
Decel Time 1 (P1.14) = 120
Start Function (P3.2.4) = Flying Start
Stop Function (P3.2.5) = Coast to Stop
Defines nominal motor voltage from motor nameplate data.
Defines nominal motor frequency from motor nameplate data.
Siemens BT300 HVAC Drive
Settings
Settings
DPD01809
2016-06-07