11. Press any button on the front panel display to activate the menu options. Select
CONTROL and GO TO BYPASS MODE.
The
indicator illuminates solid and the
UPS is operating in Bypass mode. The load is now powered by utility power.
If the
indicator is flashing, do not proceed until all alarms are clear. Check the
UPS status from the front panel to view the active alarms. Correct the alarms
and restart if necessary.
12. Switch the load connector circuit breaker to the ON (
13. Press the
ESC
button until the Start screen appears.

Standalone UPS Shutdown

To shut down a standalone UPS (see Figure 58 on page 71):
1.
Switch the load connector circuit breaker to the OFF (O) position.
NOTE The load connector breaker controls the load connector only, not the output power cord.
2.
Press any button on the front panel display to activate the menu options. Select
TURN UPS ON/OFF, TURN UPS OFF, and press the
3.
Confirm the selection. Press and hold the
UPS stops beeping.
The output relays open, the UPS transfers to Standby mode, and the
indicator turns off.
4.
Switch the UPS battery circuit breaker to the OFF (O) position.
5.
If optional EBMs are installed, switch all EBM battery circuit breakers to the
OFF (O) position.
6.
Switch the UPS input circuit breaker to the OFF (O) position.
7.
Switch off utility power where the UPS is connected.

Individual Paralleled UPS Shutdown

To shut down an individual UPS in the parallel system (see Figure 58 on page 71):
1.
Switch the load connector circuit breaker to the OFF (O) position.
NOTE The load connector breaker controls the load connector only, not the output power cord.
2.
Press any button on the front panel display to activate the menu options. Select
TURN UPS ON/OFF, TURN UPS OFF, and press the
3.
Confirm the selection. Press and hold the
UPS stops beeping.
The output relays open, the UPS transfers to Standby mode, and the
indicator turns off.
4.
Switch the UPS battery circuit breaker to the OFF (O) position.