Saia Pcd Pgu Mode; Saia Pcd Series [Pds] - KEP MMI-1500 Installation & Operation Manual

Mmi-touchscreen series
Table of Contents

Advertisement

16.36 SAIA PCD Series [PDS]

16.36.1 HMI Setting
Communication parameters must be set the same as those of the PLC. The following settings are recommended.
Parameter
Recommended Setting Notes
PLC Type

SAIA PCD PGU Mode

[PDS V1.00]
SAIA PCD S-BUS Mode
[PDS V1.00]
Serial I/F port
RS-232, RS485 2W
Baud rate
9600
Parity
Even (None – S-Bus)
Data bits
7 (8 – S-Bus)
Stop bits
1
HMI station No.
0
PLC station No.
0
Comm. delay (10msec) 0
16.36.2 PLC Setting
Communication parameters must be the same as those of the HMI
Compatible with:
SAIA PCD Series, PGU mode
SAIA PCD Series, S-Bus mode: Data (S2)
16.36.3 Wiring
16.36.3.1
Wiring for cable connections using SAIA PCD CPU with RS-232 Host Link D-Sub 9 Female Plug
ports.
KEP Part#: (Not Available) (D-Sub 9 Male Socket to D-Sub 9 Male Socket Cable)
HMI PLC[RS-232]
2 TD
3 RD
5 GND
8 RTS
P800.pds driver must be present in \drivers folder
SSbus.pds driver must be present in \drivers folder
Options: RS-232, RS-485 default/2W/4W – Dependant on PLC
hardware
Options: 9600, 19200 - Must match PLC port setting
Options: Odd, Even, None - Must match PLC port setting
Options: 7, 8 - Must match PLC port setting
Options: 1, 2 - Must match PLC port setting
Not used
Options: 0-255 - As per PLC setting
Request delay: 0~999 @10 milliseconds. Use when the PLC requires a
delay between requests. Not implemented in simulation mode.
Connect to SAIA PCD CPU RS-232 Host Link port
2 RXD
3 TXD
5 GND
6 DSR
7 RTS
8 CTS
Shield
Earth Ground
282