A-B Logix Df1 - KEP MMI-1500 Installation & Operation Manual

Mmi-touchscreen series
Table of Contents

Advertisement

16.4 A-B Logix DF1 [PDS]
16.4.1 HMI Setting
Communication parameters must be set the same as those of the PLC. The following settings are recommended.
Parameter
PLC type
Serial I/F port
Baud rate
Parity
Data bits
Stop bits
HMI station No.
PLC station No.
Comm. delay (10msec) 0
*Settings given are the default.
16.4.2 PLC Settings
Communication parameters must be the same as those of the MMI.
Full Duplex Operation must be set.
No Hardware Handshaking must be set.
Error checking must be set to CRC.
Tag structure must be set as specified below (16.4.5).
Compatible PLCs
TM
CompactLogix
, ControlLogix
16.4.3 Wiring
16.4.3.1
Wiring for cable connections using AB CompactLogix or ControlLogix CPU's with RS232 D-Sub
9 Male Socket ports.
KEP Part#: SMICABDF1-05 (D-Sub 9 Male Socket to D-Sub 9 Female Plug Cable)
HMI PLC[RS-232]
2 TD
3 RD
5 GND
9
Note: Graphic representation may not reflect the actual appearance of the finished cable.
Recommended Setting
AB Logix DF1 [PDS V2.00] ablogix.pds driver must be present in \drivers folder
RS-232
19200*
None*
8*
1*
0
1
TM
, FlexLogix 1794-L33A
Connect to AB CompactLogix or ControlLogix CPU RS-232 port Channel 0 or 1
2 RD
3 TD
5 GND
7 RTS
8 CTS
Shield
Earth Ground
Notes
Options: 9600, 19200- Must match PLC channel setting
Options: Odd, Even, None - Must match PLC channel setting
Options: 7, 8 - Must match PLC channel setting
Options: 1, 2 - Must match PLC channel setting
HMI station No. must be 0
The Station number must match the PLC Node Number (1-31)
Request delay: 0~999 @10 milliseconds. Use when the PLC requires
a delay between requests. Not implemented in simulation mode.