13.22 Recipe Transfer

The Recipe Transfer part activates the transfer of a block of contiguous registers from the HMI to the controller or
from the controller to the MMI. HMI storage address is determined by an internal word (See special note below).
Procedure to create a Recipe Transfer Part.
1. Click the Recipe Transfer Tool or select Recipe
Transfer from the Parts menu.
2. Fill in General Tab Items:
Description: A reference name (not displayed) that you
assign to the Recipe Transfer.
Write Address: Word that begins the block of registers
to write or receive upload from the PLC.
Device type is the word prefix.
Device address is the word number.
No. of words is how many registers are transferred.
Tag is used to select the Read address from a list of
predefined Tags.
Aux. directs the Read address to be retrieved from
the Auxiliary Port.
Note: When using RW words for recipe transfer functions, the range is RW00000 to RW59999. The transfer starts at
the RW address specified by RWIxxxx with offset LW9000 and continues up to the number of words specified.
Attribute:
Download moves values from the HMI retentive memory to the controller.
Save transfers values from the controller to the HMI retentive memory area.
3. Go to Shape Tab: Select Shape or Bitmap of the button to activate the transfer.
4. Go to Label Tab: Fill in fields to denote states, if desired.
5. Click OK to position the part and resize it if necessary.
Note: Refer to Section 2: Software Reference Guide for details about completing each tab item
Note: Reserved System Bits Used for Recipe Transfer
LB9010 Indicates when a download is in progress: Downloading Active (ON) or Not Downloading (OFF).
LB9011 Indicates when an upload is in progress: Uploading Active (ON) or Not Uploading (OFF).
LB9012 Indicates if the HMI is: Downloading (ON) or Uploading (OFF)
Note: System Words Used for Recipe Transfer
RWxxxx Retentive memory location: Downloads and uploads begin at the address specified by LW9000.
RWIxxxx Pointer to Retentive memory: Downloads and uploads start at the xxxx address of RWIxxxx.
LW9000 Offset Pointer to Retentive memory: Downloads and uploads begin at the xxxx address of RWIxxxx plus the