KEP MMI-1500 Installation & Operation Manual page 213

Mmi-touchscreen series
Table of Contents

Advertisement

16.1.3.3
Wiring for cable connections using AB PLC5 CPU's with RS232 D-Sub 25 Male Socket ports.
KEP Part#: (Not Available) (D-Sub 9 Male Socket to D-Sub 25 Female Plug Cable)
HMI PLC[RS-232]
2 TD
3 RD
5 GND
9
16.1.3.4
Wiring for cable connections using AB PLC5 CPU's with RS422 D-Sub 25 Male Socket ports.
KEP Part#: (Not Available) (D-Sub 9 Female Plug to D-Sub 25 Female Plug Cable)
HMI PLC[RS-485]
2 RxD+
1 RxD-
4 TxD+
3 TxD-
5 GND
16.1.3.5
Wiring for cable connections using SLC5/01, SLC5/02 CPU's with KE Module RS422 D-Sub 9
Female Plug ports.
KEP Part#: (Not Available) (D-Sub 9 Female Plug to D-Sub 9 Male Socket Cable)
HMI PLC[RS-485]
2 RxD+
1 RxD-
4 TxD+
3 TxD-
5 GND
Note: Graphic representation may not reflect the actual appearance of the finished cable.
Connect to AB PLC5 CPU's with RS232 Port
3 RX
2 TX
7 GND
4 RTS
5 CTS
6 DSR
8 DCD
20 DTR
Shield
Earth Ground
Connect to AB PLC5 CPU's with RS422 Port
14 TxD+
2 TxD-
16 RxD+
3 RxD-
7 GND
4 RTS+
5 CTS+
6 DSR+
8 DCD+
20 DTR+
22 DSR-
10 DCD-
19 RTS-
13 CTS-
Shield
Earth Ground
Connect to AB SLC5/01, SLC5/02 CPU's with KE Module RS422 Port
9 TxD+
1 TxD-
6 RxD+
2 RxD-
5 GND
Shield
Earth Ground
23 DTR-