16.5 DELTA DVP
16.5.1 HMI Setting
Communication parameters must be set the same as those of the PLC. The following settings are recommended.
Parameter
Recommended Setting
Serial I/F port
RS-232
Baud rate
9600
Parity
Even
Data bits
7
Stop bits
1
HMI station No.
0
PLC station No.
1
Comm. delay (10msec) 0
This driver supports Extended Address mode.
16.5.2 PLC Setting
Communication parameters must be set the same as those of the HMI (RS-232 port, 9600, Even parity, 7 data bits and 1
stop bit).
Compatible with:
Delta DVP-14ES, DVP-24ES, DVP-32ES, DVP-60ES
16.5.3 Wiring
16.5.3.1
Wiring for cable connections using DELTA DVP CPU's with RS232 Round 8 pin MiniDIN ports.
KEP Part#: (Not Available) (D-Sub 9 Male Socket to 8 pin MiniDIN Male Plug Cable)
HMI PLC[RS-232]
2 TD
3 RD
5 GND
9
Note: Graphic representation may not reflect the actual appearance of the finished cable.
16.5.4 Device address
Bit/Word
Type
Address Format
B
X
B
Y
B
M
B
S
B
T
B
C
W
TV
W
CV
W
CV2
W
D
Note: The PLC's memory range may vary within the range supported by the driver. Use appropriate addresses.
DVP-14ES, DVP-24ES, DVP-32ES, DVP-60ES CPU's RS-232 Port
4 RX
5 TX
8 GND
Shield
Earth Ground
Range
ooooo
ooooo: 0 ~ 23417
ooooo
ooooo: 0 ~ 23417
dddd
dddd: 0 ~ 9999
dddd
dddd: 0 ~ 9999
dddd
dddd: 0 ~ 9999
dddd
dddd: 0 ~ 9999
dddd
dddd: 0 ~ 9999
ddd
ddd: 0 ~ 127
ddd
ddd: 232 ~ 255
dddd
dddd: 0 ~ 9999
Notes
Options: RS232, RS485 – Dependant on PLC hardware
Options: 9600, 19200- Must match PLC setting
Options: Odd, Even, None - Must match PLC setting
Options: 7, 8 - Must match PLC setting
Must match PLC setting
Not used
The Station number must match the PLC Station Number (0-255)
Request delay: 0~999 @10 milliseconds. Use when the PLC requires a
delay between requests. Not implemented in simulation mode.
Octal values only - Inputs
Octal values only - Outputs
Internal Bits
Step Bits
Timer Control Bit
Counter Control bit
Timer
Single word counter
High Speed Double Word counter
Data Register
215
Notes