3. Fill in Attributes Dialog:
Address type: Select Bit or Word address type.
Read Address: Specifies the PLC bit or word address that
triggers the message.
Device type is the bit or word prefix.
Device address is the bit or word number.
For Word types select how the device data is encoded.
Data format: Defines data from the controller as binary
(BIN) or binary coded decimal (BCD).
See Word Lamp 13.2 for format description.
Aux. directs the Read address to be retrieved from the
Auxiliary Port.
Tag is used to select the Read address from a list of
predefined Tags.
Attribute:
Event Trig.
Bits: ON: displays message when bit is ON. OFF:
displays message when bit is OFF.
Words: Use "<" to trigger when value in word is less
than entered value. Use ">" to trigger when value in
word is greater than entered value. Use "==" to trigger
when value in word is the same as the entered value.
Category – Event category (reserved for future use)
Print:
On Trig.: Prints out message when event is triggered.
Return to normal: Prints out message when the event
returns to normal state.
Text:
Fill in the fields as described below.
Item
Content
Color
Font
Use Label Library
Label Library ...
Write Value
Note: Data from Local Words can be embedded in an Event message for printing only. To embed values use the %nnd
format. For display, the message is blank where the word data is displayed.
To print out current value of PLC register data, first assign a Recipe transfer object or PLC Control/General Control to
move data from the PLC to internal (LW) memory.
Where:
The starting delimiter
%
An internal register (LW) number 00-99
nn
The ending delimiter
d
For example: The Content field is set as "Current temperature value %25dF: HIGH ALARM"
If LW25 = 120 then the message are printed out as "Current temperature value 120F: HIGH ALARM".
Description
Directly entered text message or Label from Label Library. See note on embedding values.
Color of the text when displayed in the Event Display part.
Font size, 16 or 24 point. Default is 16.
Select to use a predefined Label form the Label Library instead of directly entered text.
Click to call up the Label Library for editing or adding Labels.
A value to be written to the Write address of the Event Display when the event is acknowledged.