Omron / Omron (485 2W) Host Link - KEP MMI-1500 Installation & Operation Manual

Mmi-touchscreen series
Table of Contents

Advertisement

16.33 OMRON / OMRON (485 2W) Host Link

16.33.1 HMI Setting
Communication parameters must be set the same as those of the PLC. The following settings are recommended.
Parameter
PLC Type
Serial I/F port
Baud rate
Parity
Data bits
Stop bits
HMI station No.
PLC station No.
Comm. delay (10msec) 0
OMRON(485 2W) supports Extended Address mode.
16.33.2 PLC Setting
Host Link Protocol Communication parameters must be the same as those of the HMI
Set Station Number as "00" if not using Extended Address mode or RS232 connections.
Compatible with:
SYSMAC C-Series: C200H, C60K, C40K/H, C28K/H, C20K/H, and C200H/HS/ALPHA
CQM1 Series: CQM1, CPM1/1H, CPM2A, and SRM1
Communication Module: CPM1-CIF01 adapter (for CPM1/CPM1A/CPM2A series, CQM1/CQM1H series)
Communication Module: CPM1H-SCB41 communication module (for CQM1H-CPU51/61)
Communication Module: C200h-LK201, 3G2A6-LK201
Communication Module: C200HW-COM02/03/04/05/06
16.33.3 Wiring
16.33.3.1
Wiring for cable connections using OMRON C20H, C28H, and C40H CPU's and C200HW-
COM02/03/04/05/06 Modules with RS-232 Host Link D-Sub 9 Female Plug ports.
KEP Part#: (Not Available) (D-Sub 9 Male Socket to D-Sub 9 Male Socket Cable)
HMI PLC[RS-232]
2 TD
3 RD
5 GND
Recommended Setting Notes
OMRON
OMRON(485 2W)
RS-232, RS485 2W
9600
Even
7
1
0
0
Connect to OMRON C20H, C28H, and C40H CPU RS-232 Host Link port
3 RD
2 TD
7 GND
4 RS
5 CS
1
Shield
Earth Ground
Does not support Extended Address mode
Supports Extended Address mode
Options: RS-232, RS-485 default/2W/4W – Dependant on PLC
hardware
Options: 9600, 19200, 38400, 57600, 115200 - Must match PLC port
setting
Options: Odd, Even, None - Must match PLC port setting
Options: 7, 8 - Must match PLC port setting
Options: 1, 2 - Must match PLC port setting
Not used
Options: 0-255 - As per PLC setting if not using Extended Addressing
Request delay: 0~999 @10 milliseconds. Use when the PLC requires a
delay between requests. Not implemented in simulation mode.