KEP MT8072iP Series Installation Instructions

Advertisement

Quick Links

MT8072iP series
1
Installation and Startup Guide
This document covers the installation of MT8072iP Series HMI, for the detailed specifications and
operation, please refer to Datasheet, Brochure and EasyBuilder Pro User Manual. Please read all warnings,
precautions, and instructions on the device carefully before use.
Install Environment:
NEMA Rating
The HMI product is NEMA 4 rated (Indoor Only).
The HMI product has been tested to conform to European CE requirements. This
Electrical
means that the circuitry is designed to resist the effects of electrical noise. This
does not guarantee noise immunity in severe cases. Proper wire routing and
Environment
grounding will insure proper operation.
(1) Make sure that the displays are installed correctly and that the operating
limits are followed. Avoid installing units in environments where severe
mechanical vibration or shocks are present.
(2) Do not operate the unit in areas subject to explosion hazards due to
Environmental
flammable gases, vapors or dusts.
(3) Do not install the unit where acid gas, such as SO2 exists.
Considerations
(4) This device should be mounted in the vertical position and for use on the flat
surface enclosure.
(5) For use in Pollution Degree 2 Environment and dry location.
(6) Relative Humidity: 10% ~ 90% (non-condensing)
Cleaning
Clean the device using dry cloths. Do not use liquid or spray detergents for
Considerations
cleaning.
IP Rating
IP 65
Protection impairment if used in a manner not specified by the manufacturer.
Warning
Déficit de protection si utilisé d'une manière non spécifiée par le fabricant.
2
Unpacking the Unit
Unpack and check the delivery. If damage is found, please contact the supplier.
NOTE: Place the operator panel on a stable surface during installation. Dropping it or letting it fall
may cause damage.
(1) Installation Instruction, 2-sided A4 *1
(2) Human Machine Interface *1
(3) Power Connector *1
(4) Brackets & Screws *1 pack
3
Installation Instructions
Use a control box that provides enough stiffness. Secure the operator panel in position, using all the
fastening holes and the provided brackets and screws. Screw Torque: 2.6 ~ 3.9 lbf.in. (For reaching
waterproof effect and preventing the panel from being deformed.)
Plan for adequate space around the unit and inside the enclosure, for ventilation and cables. Consider the
heat from other devices inside the enclosure. The ambient temperature around the unit must be 0 ~ 55°C
Minimum required clearances (along the overlay): Top 15 mm / Bottom 50 mm / Sides 15 mm
Maximum panel thickness: 4.5 mm
Installation Instruction
(A)
Cutout
(B)
Type
A(mm)
B(mm)
MT8072iP
192
138
4
Power Connections
Power Connector Specifications:
Wire AWG: 24~12
Wiring Conductor Minimum Temperature: 75°C
Screw Torque: 4.5 lbf-in (max.)
Copper conduct only.
NOTE:
1. Connect positive DC line to the '+' terminal and the
DC ground to the '-' terminal.
2. When downloading project using a USB cable, do not
connect HMI with PLC and PC simultaneously, for
electric potential difference may result in damage to HMI or PC.
System Settings
5
When HMI is powered up and displays image, click the system setting button. (Default System Password:
111111)
Go to Security tab, the default password is 111111, click the buttons to set your own passwords.
In MISC2 tab, if "Enable [Reset HMI to default] button in calibration mode" is selected, the [RESET HMI TO
DEFAULT] button can be found in calibration mode, as shown in Part 8.

Advertisement

loading

Summary of Contents for KEP MT8072iP Series

  • Page 1 B(mm) MT8072iP This document covers the installation of MT8072iP Series HMI, for the detailed specifications and operation, please refer to Datasheet, Brochure and EasyBuilder Pro User Manual. Please read all warnings, precautions, and instructions on the device carefully before use.
  • Page 2 EasyBuilder Pro Software Settings NOTE: Make sure that all local and national electrical standards are met when CAUTION installing the unit. Contact your local authorities to determine which codes apply. Launch EasyBuilder Pro software, select your project file, press F7 shortcut key to open the download Use power output that meets SELV (Safety Extra-Low Voltage) requirements.