16.23.1 HMI Setting
Communication parameters must be set the same as those of the PLC. The following settings are recommended.
Parameter
Recommended Setting Notes
Serial I/F port
RS232
Baud rate
38400
Parity
None
Data bits
8
Stop bits
1
HMI station No.
0
PLC station No.
0
Comm. delay (10msec) 0
16.23.2 PLC Setting
Communication parameters must be the same as those of the MMI.
Compatible with:
LG MASTER-K series: K80S, K200S, K300S, K1000S
16.23.3 Wiring
16.23.3.1
Wiring for cable connections using LG MASTER-K Series K80S, K200S, K300S, K1000S CPU's
with RS232 D-Sub 9 Male Socket ports.
KEP Part#: ZA9M9F (D-Sub 9 Male Socket to D-Sub 9 Female Plug Cable)
HMI PLC[RS-232]
2 TXD
3 RXD
5 GND
Note: Graphic representation may not reflect the actual appearance of the finished cable.
16.23.4 Device address
Bit/Word Type Address Format
B
P
B
K
B
M
B
L
B
F
W
TV
W
CV
W
D
Note: The PLC's memory range may vary within the range supported by the driver. Use appropriate addresses.
Options: 9600, 19200, 38400 - Must match PLC port setting
Options: Odd, Even, None - Must match PLC port setting
Options: 7, 8 - Must match PLC port setting
Options: 1, 2 - Must match PLC port setting
Not used
Must match PLC port setting (0-31)
Request delay: 0~999 @10 milliseconds. Use when the PLC requires a
delay between requests. Not implemented in simulation mode.
Connect to LG MASTER-K K80S, K200S, K300S, K1000S CPU RS-232 port
2 RXD
3 TXD
5 GND
Shield
Earth Ground
Range
dddh
ddd: 0~255 h: 0~F I/O Relay, Word portion is decimal, bit portion is
dddh
ddd: 0~255 h: 0~F Keep Relay, Word portion is decimal, bit portion is
dddh
ddd: 0~255 h: 0~F Auxiliary Relay, Word portion is decimal, bit portion is
dddh
ddd: 0~255 h: 0~F Link Relay, Word portion is decimal, bit portion is
dddh
ddd: 0~255 h: 0~F Special Relay, Word portion is decimal, bit portion is
ddd
ddd: 0~255
ddd
ddd: 0~255
dddd
dddd: 9999
hexadecimal
hexadecimal
hexadecimal
hexadecimal
hexadecimal
Timer Accumulator
Counter Accumulator
Data Registers
248