16.18.1 HMI Setting
Communication parameters must be set the same as those of the Controller. The following settings are recommended.
Parameter
Recommended Setting Notes
Serial I/F port
RS485
Baud rate
9600
Parity
Even
Data bits
8
Stop bits
1
HMI station No.
0
PLC station No.
1
Comm. delay (10msec) 0
16.18.2 PLC Setting
Communication parameters must be the same as those of the MMI.
Compatible Models:
8200 Vector with LECOM A/B module 2102IB
9300 Vector with LECOM A/B module 2102IB
16.18.3 Wiring
Wiring for cable connections to 9300/8200 series controllers with pass-through 2102IBV001:RS232/485 interface.
16.18.3.1
Wiring for cable connections using Lenze Controller with LECOM-B RS485 Plug in terminal ports.
KEP Part#: (Not Available) (D-Sub 9 Male Socket to 4 pole Plug Cable)
HMI PLC[RS-485]
1 RXD-
2 RXD+
16.18.4 Device address
Bit/Word
Type
Address Format
B
CNB
W
CI
DW
CD
DW
CF
W
CNI
DW
CND
DW
CNF
Note: The PLC's memory range may vary within the range supported by the driver. Use appropriate addresses.
Options: 9600, 19200- Must match Controller port setting
Options: Odd, Even, None - Must match Controller port setting
Options: 7, 8 - Must match Controller port setting
Options: 1, 2 - Must match Controller port setting
Or must not match Controller port setting (0-255)
Or must match Controller port setting (0-255)
Request delay: 0~999 @10 milliseconds. Use when the PLC requires a
delay between requests. Not implemented in simulation mode.
Connect to Lenze Controller with RS485 Port
71 T/R(B)-
72 T/R(A)
Shield
Earth Ground
ddddbb
dddd: 0~9999, bb: 0~15
dddd(dd)
dddd: 0~8192 dd:00~99
dddd(dd)
dddd: 0~8192 dd:00~99
dddd(dd)
dddd: 0~8192 dd:00~99
dddd
dddd: 0~9999
dddd
dddd: 0~9999
dddd
dddd: 0~9999
Range
Always use 2 digits for bit designation
16 Bit values
32 Bit Values
32 Bit Floating Point Values
16 Bit values
32 Bit Values
32 Bit Floating Point Values