11.1.4 System Error Messages

A running project (simulation or after download) displays error messages when various fault conditions occur. Below is a list
of these messages.
Message
Attach Fail Suggest Reset PLC
Attach PLC
Base Window<##> Must Full
Screen Size
BCD Transfer Overflow
Invalid Window Number <##>
MilliSecond Timer Full
Not Support Operation
Object Queue Full
PLC Data Block Queue Full
PLC no response *
PLC responsed always delayed.
PLC response error*
Printer fail!
Printer pool overflow
Project image error, compiler
again
Second Timer Full
System Severe Error*
System severe error
(error code 10002)
System severe error
(error code 10013)
System severe error
(error code 10101)
Text Index Out of Range:
Font Style <##>
This PLC Only Support Read
<##> Words of Word of BIT Data
This PLC Only Support Read
<##> Words of Word Data
Description
Cannot setup communication with PLC, cycle power to the PLC to clear its buffer
and retry.
Cannot detect the PLC. Check the cable connections and PLC port settings.
Initiate communications with the PLC.
Attempting to open a Base window number <##> that is less than full size.
Occurs when attempting to enter an illegal data value into a BCD type register
(such as entering 10000 to a 16-bit BCD register).
A change screen command issued by either Function Key or PLC Control is
attempting to switch to undefined screen: <##> (screen number).
Out of system resources – check factory
Attempting to do something that is not allowed for the driver.
Out of system resources – check factory
The PLC data points on a screen cannot be divided into less than 100 read blocks.
(100 is the limit of read blocks)
HMI lost communication with PLC, incorrect cable configuration to PLC or incorrect
System Parameter settings for PLC.
PLC reply timing was off. Try to adjust response time in the PLC if this is possible;
if not, report problem to KEP.
PLC replied with an unexpected response message, caused by a read command
or write command. Check if the configured PLC device address is available.
The printer is not ready or the printer buffer is full.
The printer buffer is full. Check that the printer is on line and responding.
There is an error in the compiled project file (*.eob). Check the project compile
level and recompile the project.
Out of system resources – check factory
System has run out of memory – check factory
System cannot uncompress a graphic because it is larger than 250KB. Do not
compress bitmaps larger than 250KB. Change System Parameter/Editor
Tab/Object In Compress to "No".
Attempt to use an external driver with Hardware that is not enabled to accept it.
Contact the factory for assistance.
System Parameter/General Tab/Startup window is an undefined window. Change
the Startup window number to a valid window.
The text string contains illegal values that access characters out of the font table
range. <##> denotes the illegal character code.
A part is attempting to read more bit data from the PLC than the driver can handle.
Reduce the number of bits on the screen or adjust the Block Pack.
A part is attempting to read more data from the PLC than the driver can handle.
Reduce the number of words assigned to the part or adjust the Block Pack.