Periodic Test; General Guidance; Conducting A Periodic Test - Visonic PowerMaster-10 Installer's Manual

Fully supervised wireless alarm control system
Hide thumbs Also See for PowerMaster-10:
Table of Contents

Advertisement

4 PERIODIC TEST

4.1 General Guidance

This mode provides you with the means to conduct a periodic test, via the PERIODIC TEST menu, at least once
a week and after an alarm event.
When you are instructed to perform "periodic test", walk throughout the site to check the detectors / sensors
(except for Sirens and Temperature Sensors). When a detector/sensor is triggered into alarm, its name, number
and the alarm reception level should be indicated (for example, "Bathroom", "Z19 strong") and the buzzer should
sound according to the alarm reception level (1 of 3). Each device should be tested according to the device
Installation Instructions.
To enter the
PERIODIC TEST
Step 1
[1]
READY
PERIODIC TEST
(enter installer /
master code)
– Entering the "Periodic Test" Menu
To Select an Option:
[1]
Enter the
PERIODIC TEST
[2]
Select the test to perform, for example:

4.2 Conducting a Periodic Test

The PowerMaster-10 / PowerMaster-30 enables you to conduct the periodic test in four parts:
Siren Test: Each siren of the system is automatically activated for 3 seconds (outdoor sirens with low volume).
Temperature Sensor Test: When Temperature Sensors are enrolled in the system, the control panel displays
the temperature of each zone in Celsius or Fahrenheit.
Test all devices: All devices are tested.
Other Device Test: Each of the other devices in the system is activated by the installer and the display
indicates which devices were not yet tested. The "it's me" indication helps to identify the untested devices if
necessary. A counter also indicates the number of devices that remain untested.
READY
To conduct a periodic test, make sure the system is disarmed and then enter the
using your installer code (8888 by default) or master installer code (9999 by default). Immediately after entering
the "Periodic Test" menu, all 4 LED's on the panel will momentarily light (LED test).
Option
SIRENS TEST
D-303222 PowerMaster-10 / PowerMaster-30 Installer's Guide
menu and to conduct a periodic test, proceed as follows:
Step 2
Select the test you want to
perform [2]
SIRENS TEST
TEMPERATURE TEST
TEST ALL DEVICES
TEST ONE DEVICE
menu using your installer or master code.
TEMPERATURE TEST
PERIODIC TEST
Instructions
Here you can test the sirens.
To initiate the siren test press
where "N" indicates the zone location assigned to the siren that is currently being
tested. [1]
and then press
OPTION you wish
. The display now reads
.
Means
and
scroll
select
menu
PERIODIC TEST
SIREN N
,
79