6. PERIODIC TEST

Option
6. PERIODIC TEST

6.1 General Guidance

This mode provides you with the means to conduct a periodic test, via the "PERIODIC TEST" menu, at least once a
week and after an alarm event.
When you are instructed to perform a periodic test, walk throughout the site to check the detectors / sensors (except for
Sirens and Temperature Sensors). When a detector/sensor is triggered into alarm, its name, number and the alarm
reception level should be indicated (for example, "Bathroom", "Z19 strong") and the buzzer should sound according to
the alarm reception level (1 of 3). Each device should be tested according to the device Installation Instructions.
To enter the "PERIODIC TEST" menu and to conduct a periodic test, proceed as follows:
Step 1
READY
PERIODIC TEST
(enter installer /
master code)
– Periodic Test
[1]
Not including Siren and Temperature Sensors
[2]
After reviewing all untested devices the control panel will read "<OK> TO LEAVE". You can now do one of the
following: press
to exit the testing procedure.

6.2 Conducting a Periodic Test

The PowerMaster enables you to conduct the periodic test in four parts:
Siren Test: Each siren of the system is automatically activated for 3 seconds (outdoor sirens with low volume).
Temperature Sensor Test: When Temperature Sensors are enrolled in the system, the control panel displays the
temperature of each zone in Celsius or Fahrenheit.
Test all devices: All devices are tested.
Other Device Test: Each of the other devices in the system is activated by the installer and the display indicates which
devices were not yet tested. The "it's me" indication helps to identify the untested devices if necessary. A counter also
indicates the number of devices that remain untested.
⋅ ⋅ ⋅
READY
To conduct a periodic test, make sure the system is disarmed and then enter the "PERIODIC TEST" menu using your
installer code (8888 by default) or master installer code (9999 by default). Immediately after entering the
"PERIODIC TEST" menu, all 4 LED's on the panel will momentarily light (LED test).
Option
SIRENS TEST
68
Configuration Instructions
"cancel alarm" time, a "cancel alarm" message is sent to the Monitoring Station indicating that
the alarm was canceled by the user.
Options: not active (default in USA); in 1/5 (default)/15/60 minute(s) and in 4 hours.
Step 2
[1]
Select the test to be performed
SIRENS TEST
TEMPERATURE TEST
TEST ALL DEVICES
TEST ONE DEVICE
to abort the testing procedure; press
PERIODIC TEST
Instructions
You can test wireless sirens and strobes (including the control panel siren) and sirens of
smoke sensors.
To initiate the siren test press
zone location assigned to the siren that is currently being tested.
First the panel siren sounds for 3 seconds after which the PowerMaster system will
automatically repeat the procedure for the next siren enrolled in the system until all sirens are
tested. You should listen to the sirens sounds and make sure that all sirens sound.
Once all the sirens have been tested, the control panel will now test the sirens of smoke
sensors that are enrolled in the alarm system. The display now reads "Zxx: SMOKE SIREN",
where "Zxx" indicates the zone number of the smoke sensor, and alternates with "<OK> TO
[2]
to continue the testing procedure; or press
⋅ ⋅ ⋅
MENU you wish
. The display now reads "SIREN N". "N" indicates the
D-304762 PowerMaster-10/30 G2 Installer's Guide