Perform Frequency Setting By Analog (current Input) - Mitsubishi Electric FR-F700 Series Instruction Manual

Fr-f700 series.
Hide thumbs

Advertisement

Operation by the start command from
the operation panel (PU operation mode)
3.5.5

Perform frequency setting by analog (current input)

POINT
· Use
/
to give a start command.
· Turn the AU signal on.
· Pr. 79 Operation mode selection must be set to "4" (external/PU combined operation mode 2)
[Connection diagram]
AU signal
adjustment meter
Operation
1.
Screen at powering on
The monitor display appears.
2.
Press
to choose the parameter setting mode.
3.
Turn
until
4.
Press
to read the currently set value.
" "(initial value) appears.
5.
Turn
clockwise to change it to the setting
value of "
".
6.
Press
to set.
7.
Mode/monitor check
Press
twice to choose the monitor/frequency
monitor.
8.
Start
Check that the terminal 4 input selection signal
(AU) is on.
Press the start switch
FWD or REV of operation status indication flickers.
CAUTION
When both the forward switch and reverse
switch turn on, the inverter will not start.
Also, if both switch turn on while running,
the inverter stops.
40
Three-phase
R/L1
S/L2
AC power supply
T/L3
AU
SD
Output of the
4(+)
5(-)
(4 to 20mADC)
(Pr. 79) appears.
(or
).
Inverter
U
V
Motor
W
FR-DU07
,
Display
Flicker ··· Parameter setting complete!!
(
)
The parameter number
read previously appears.
Flickering