PRODUCT SPECIFICATIONS
14-2
EATON Powerware
14.2.2

UPS System Output

UPS Output Capacity
Output Voltage Regulation
Output Voltage Adjustment
(Nominal +/–3%)
Output Voltage Harmonic
Content
Output Current
Output Voltage Balance
Output Voltage Phase
Displacement
Output Transients
Frequency Regulation
Synchronous to Bypass
Frequency Slew Rate
Overload Current Capability
14.2.3

Environmental

Operating Temperature
Operating Altitude
Storage Temperature
Relative Humidity (operating
and storage)
Acoustical Noise
EMI Suppression
Electrostatic Discharge (ESD)
Immunity
®
9390 UPS (20–80 kVA) Installation and Operation Manual
100% rated current

1% (10% to 100% load)
208 Vac nominal, adjustable from 202 Vac to 214 Vac
220 Vac nominal, adjustable from 214 Vac to 226 Vac
380 Vac nominal, adjustable from 369 Vac to 392 Vac
400 Vac nominal, adjustable from 388 Vac to 412 Vac
415 Vac nominal, adjustable from 403 Vac to 428 Vac
480 Vac nominal, adjustable from 466 Vac to 494 Vac
1.5% max THD (linear load)
5% max THD (nonlinear load)
See Appendix A, Table G through Table I.
3% for 100% maximum load imbalance (linear load)
3° for 100% maximum load imbalance (linear load)
"5% for 100% load step or removal
"0.01 Hz free running
Bypass within voltage limits of +5%, –8% of output setting; bypass
within "0.5 Hz
1 Hz per second maximum
102% for 10 minutes 100–101.9%
110% for 30 seconds 102–109.9%
125% for 10 seconds 110–124.9%
>125% for 10 cycles
0 to 40°C (32–104°F) without derating, excluding batteries. The
recommended operating temperature is 25°C (77°F).
Maximum 1500m (5000 ft) at 40°C without derating
–25 to +60°C, excluding batteries (prolonged storage above 40°C
causes rapid battery self‐discharge)
5% to 95% maximum noncondensing
65 dB at a 1m distance, c weighted
EN62040-2:2006 CATC3
Meets IEC 801‐2 specifications. Withstands up to 25 kV pulse without
damage and with no disturbance or adverse effect to the critical load.