INSTALLATION INFORMATION
16.
Conduit must be installed between the UPM cabinets for parallel interface wiring. Install the
interface wiring in separate conduit from the power wiring.
17.
Use Class 1 wiring methods (as defined by the NEC) for parallel interface wiring. The wire
should be shielded twisted pair, rated for 5 amps maximum.
18.
See Table AC and Chapter 6 for parallel interface wiring.
Table AC. Powerware Hot Sync
Terminal J3
1
2
3
4
5
6
7
8
9
10
NOTE
All interface wiring is to be
provided by the customer.
A-50
EATON Powerware
CAN Bridge Card Interface Connections
®
Name
Alarm
Alarm Rtn
Not Used
Not Used
Not Used
TX
TX
CAN L
CAN H
Shield
J3
CONNECTIONS FOR PARALLEL SYSTEM CONTROL
CONNECTIONS FOR RMP , RIM, OR SCM
(ONLY ONE DEVICE CAN BE CONNECTED AT A TIME)
BUILDING ALARM 2 REPLACEMENT

POWERWARE HOT SYNC CAN BRIDGE CARD

®
9390 UPS (20–80 kVA) Installation and Operation Manual
Description
Programmable UPS alarm. Activated by a remote
dry contact closure.
Not Used
Not Used
Not Used
Remote Monitor Panel (RMP), Relay Interface
Module (RIM), or Supervisory Contact Module
(SCM) connections.
Computer Area Network (CAN) Input for parallel
operation.
DESCRIPTION:
INTERFACE WIRING INSTALLATION
NOTES AND TERMINAL LOCATIONS
DRAWING NO:
164201603-8
REVISION:
A
S
164201603 Rev 2 www.powerware.com
SHEET:
9 of 15
DATE:
091505