INSTALLATION INFORMATION
Table L. UPS Cabinet Power Cable Terminations for the Powerware 9390-40/20,
9390-40/30, and 9390-40/40 (208V/220V Input and 208V/220V Output and
380V/400V/415V/480V Input and 380V/400V/415V/480V Output)
Terminal Function
AC Input to UPS Rectifier
and Bypass
(Single Input)
AC Input to UPS Rectifier
(Dual Input)
AC Input To Bypass
(Dual Input)
Single‐Feed To Dual‐Feed
Remove Jumpers between
Rectifier Input Terminals
and Bypass Input
Terminals
AC Output to
Critical Load
DC Input from
Battery to UPS
Input and Output Neutral
Customer Ground
NOTE
A-18
EATON Powerware
Terminal Function
E6
E7
E8
E1
E2
E3
E6
E7
E8
E9
E10
E11
E4
E5
E12
Ground
Customer ground can be run in any conduit listed in Table N.
®
9390 UPS (20–80 kVA) Installation and Operation Manual
Size of Pressure
Termination
Phase A
1 - #14-2/0
Phase B
1 - #14-2/0
Phase C
1 - #14-2/0
Phase A
1 - #14-2/0
Phase B
1 - #14-2/0
Phase C
1 - #14-2/0
Phase A
1 - #14-2/0
Phase B
1 - #14-2/0
Phase C
1 - #14-2/0
Phase A
N/A
Phase B
N/A
Phase C
N/A
Phase A
1 - #14-2/0
Phase B
1 - #14-2/0
Phase C
1 - #14-2/0
Positive
1 - #14-2/0
Negative
1 - #14-2/0
Neutral
4 - #14-1/0
Ground
8 - #14-1/0
DESCRIPTION:
POWER WIRING INSTALLATION NOTES
DRAWING NO:
164201603-5
REVISION:
C
S
164201603 Rev 2 www.powerware.com
Tightening
Type
Torque
Screw
Nm (lb in)
13.5 (120)
3/16 in. Hex
13.5 (120)
3/16 in. Hex
13.5 (120)
3/16 in. Hex
13.5 (120)
3/16 in. Hex
13.5 (120)
3/16 in. Hex
13.5 (120)
3/16 in. Hex
13.5 (120)
3/16 in. Hex
13.5 (120)
3/16 in. Hex
13.5 (120)
3/16 in. Hex
5.6 (50)
1/4–20 Hex Nut
5.6 (50)
1/4–20 Hex Nut
5.6 (50)
1/4–20 Hex Nut
13.5 (120)
3/16 in. Hex
13.5 (120)
3/16 in. Hex
13.5 (120)
3/16 in. Hex
13.5 (120)
3/16 in. Hex
13.5 (120)
3/16 in. Hex
5.6 (50)
Slotted
5.6 (50)
Slotted
SHEET:
DATE:
071608
8 of 23