NOTE Interface wiring and conduit between the REPO switch
and the UPS are to be supplied by the customer.
114.3
[4.50]
Front View
Contact Block (Back View, Faceplate Removed)
Dimensions are in millimeters [inches]
EATON Powerware
115.8
[4.56]
DESCRIPTION:
DRAWING NO:
REVISION:
®
9390 UPS (20–80 kVA) Installation and Operation Manual
0.87
[0.22]
1.57
[0.40]
NEEDED
TO
REMOVE
KEY
KNOCKOUT PATTERN
TYPICAL 5 SIDES
NOTE
1. Conduit and wiring between the
Remote Emergency Power‐off (REPO)
and the UPS to be supplied by the
customer.
2. Maximum distance between the
Remote EPO and the UPS not to exceed
500 feet.
3. Maximum wire size #14 AWG.
Minimum wire size #22 AWG.
OPTIONAL REMOTE EMERGENCY
POWER‐OFF
164201603-10
B
S
164201603 Rev 2 www.powerware.com
INSTALLATION INFORMATION
88.9
[3.50]
95.3
[3.57]
SHEET:
1 of 1
DATE:
071608
A-61