PART 1 - GENERAL
1.01
SUMMARY
A.
This specification describes a three-phase continuous duty, on-line, double conversion,
solid-state uninterruptible power system, hereafter referred to as the UPS. The UPS
shall operate in conjunction with the existing building electrical system to provide power
conditioning, back-up and distribution for critical electrical loads. The UPS shall consist
of, as required by the project, the UPS module, battery cabinet(s), and accessory
cabinet(s) for transformers, maintenance bypass, parallel tie, and distribution
applications, and other features as described in this specification.
1.02
UPS SYSTEM DESCRIPTION
A.
UPS System Components: The UPS system shall consist of the following main
components:
1.
2.
3.
4.
B.
UPS Module Modes of Operation: The UPS Module shall operate as an on-line, fully
automatic system in the following modes:
1.
2.
3.
4.
5.
Static Uninterruptible Power Supply
October 9, 2009
STATIC UNINTERRUPTIBLE POWER SUPPLY
GUIDE SPECIFICATION
Model Eaton 9390 20-160 kVA
UPS module containing a Rectifier, Inverter, Battery Charger, Static Bypass, and
associated Control and Monitor Panel.
Battery string(s) in Line-and-Match Battery Cabinets.
Line-and-Match accessory cabinets for transformer, maintenance bypass,
parallel tie, and distribution applications.
Non-matching wall mounted or floor standing maintenance bypass cabinets or
multi-module parallel tie cabinets.
Normal: Utilizing commercial AC power, the critical load shall be continuously
supplied by the Inverter. The Inverter shall power the load while regulating both
voltage and frequency. The Rectifier shall derive power from the commercial AC
source and shall supply DC power to the Inverter. Simultaneously, the Battery
Charger shall charge the battery.
Battery: Upon failure of the commercial AC power, the critical load shall continue
to be supplied by the Inverter, which shall obtain power from the batteries without
any operator intervention. There shall be no interruption to the critical load upon
failure or restoration of the commercial AC source.
Recharge: Upon restoration of the AC source, the Charger shall recharge the
batteries and simultaneously the Rectifier shall provide power to the Inverter.
This shall be an automatic function and shall cause no interruption to the critical
load.
Bypass: If the UPS module must be taken out of the Normal mode for overload,
load fault, or internal failures, the static bypass switch shall automatically transfer
the critical load to the commercial AC power. Return from Bypass mode to
Normal mode of operation shall be automatic. No-break transfer to and from
Bypass mode shall be capable of being initiated manually from the front panel.
Energy Saver: The UPS shall continuously monitor the voltage and frequency of
the bypass source. When the source parameters are within acceptable limits, the
Page 1 of 1
Eaton 9390 Guide Specification

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 9390 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Eaton 9390

  • Page 1 STATIC UNINTERRUPTIBLE POWER SUPPLY GUIDE SPECIFICATION Model Eaton 9390 20-160 kVA PART 1 - GENERAL 1.01 SUMMARY This specification describes a three-phase continuous duty, on-line, double conversion, solid-state uninterruptible power system, hereafter referred to as the UPS. The UPS shall operate in conjunction with the existing building electrical system to provide power conditioning, back-up and distribution for critical electrical loads.
  • Page 2 The manual shall include the following major items: UPS description UPS site planning and unpacking UPS installation Optional accessory installation UPS theory of operation Operating procedures System events UPS maintenance Static Uninterruptible Power Supply Page 2 of 2 Eaton 9390 Guide Specification October 9, 2009...
  • Page 3: Environmental Requirements

    Relative Humidity (operating and storage): 95% maximum non-condensing. Elevation: Operational: 6600 ft (2000 m) maximum without de-rating. Transportation: Capable of air transport. Static Uninterruptible Power Supply Page 3 of 3 Eaton 9390 Guide Specification October 9, 2009...
  • Page 4 The bypass shall feature the following transfer and operational characteristics. Transfers to bypass shall be automatically initiated for the following conditions: Output overload period expired. Static Uninterruptible Power Supply Page 4 of 4 Eaton 9390 Guide Specification October 9, 2009...
  • Page 5 Testing the batteries shall not jeopardize the operation of the critical load. Upon detection of the battery string(s) not capable of providing 80%, the Static Uninterruptible Power Supply Page 5 of 5 Eaton 9390 Guide Specification October 9, 2009...
  • Page 6 Two (2)-module parallel redundant tie cabinet in a Line-and-Match configuration. SNMP Network Adapter and UPS Power Monitoring Software: SNMP adapters shall provide a communications interface between the UPS module and SNMP-compatible Static Uninterruptible Power Supply Page 6 of 6 Eaton 9390 Guide Specification October 9, 2009...
  • Page 7 Cabinet shall also have the ability to house a(n) (optional) main output breaker and a(n) (optional) bypass breaker. Cabinet Static Uninterruptible Power Supply Page 7 of 7 Eaton 9390 Guide Specification October 9, 2009...
  • Page 8 Input current total harmonic distortion (THD) shall be less than 4.5%. Power walk-in: Ramp-up to full utility load adjustable from 3 seconds to 60 seconds. Bypass input: Static Uninterruptible Power Supply Page 8 of 8 Eaton 9390 Guide Specification October 9, 2009...
  • Page 9 AC voltage failure. The time window before battery disconnection occurs shall be programmable for both time and voltage. UPS output in normal mode Static Uninterruptible Power Supply Page 9 of 9 Eaton 9390 Guide Specification October 9, 2009...
  • Page 10 The UPS shall withstand a 25 kV pulse without damage and with no disturbance or adverse effect to the critical load. Efficiency: The UPS efficiency shall be up to 94%. Static Uninterruptible Power Supply Page 10 of 10 Eaton 9390 Guide Specification October 9, 2009...
  • Page 11: Mechanical Design

    Enclosures: The UPS shall be housed in free-standing double front enclosures (safety shields behind doors) equipped with casters and leveling feet. The enclosures shall be Static Uninterruptible Power Supply Page 11 of 11 Eaton 9390 Guide Specification October 9, 2009...
  • Page 12: Controls And Indicators

    BATTERY: This shall indicate that the commercial AC utility or generator source has failed and the battery is supplying power to the inverter, which is supporting Static Uninterruptible Power Supply Page 12 of 12 Eaton 9390 Guide Specification October 9, 2009...
  • Page 13 The system shall have options to add four (4) additional building alarms, 384 logged events, 4 additional languages, Mandarin or Russian as a primary language. 2.08 COMMUNICATIONS Static Uninterruptible Power Supply Page 13 of 13 Eaton 9390 Guide Specification October 9, 2009...
  • Page 14 (if standard battery pack is provided) or external protective device for an external battery. Electronic current limiting circuitry and fuses in the Inverter circuit shall provide output protection. Static Uninterruptible Power Supply Page 14 of 14 Eaton 9390 Guide Specification October 9, 2009...
  • Page 15: Installation

    Check the DC link holding voltage, AC output voltages, and output waveforms. Check the final DC link voltage and Inverter AC output. Adjust if required. Check for the proper synchronization. Static Uninterruptible Power Supply Page 15 of 15 Eaton 9390 Guide Specification October 9, 2009...
  • Page 16: Warranty

    Manufacturer shall also provide an optional battery service plan to provide parts-and-labor coverage for partial and full battery strings, either with preventive maintenance or replacement coverage. Static Uninterruptible Power Supply Page 16 of 16 Eaton 9390 Guide Specification October 9, 2009...