Eaton 9PHD UPS 30–200 kW
Voltage tolerance without transform-
ers, (Rectifier input)
Voltage tolerance without transformers
(Bypass input)
Rated input frequency
Frequency tolerance
Number of input phases (rectifier & by-
pass)
Input power factor
Rated mains input current
Maximum mains input current
Input current distortion at rated input
current, iTHD
Rectifier ramp-up, rectifier start and
load step
Backfeed protection
9.3
Number of output phases
Rated output voltage
Rated output frequency
Total voltage harmonic dis-
tortion:
100 % linear load
100 % non-linear load
©
Eaton Corporation plc 2017. All rights reserved.

UPS system output

9PHD 30-200 kW
3 phases + N + PE or
3 phases + PE as an
option
220/380 V; 230/400 V;
240/415 V; 254/440;
277/480 V, configurable.
208–690 V available with
optional transformers
50 or 60 Hz, user
configurable
< 1%
< 5%
380-415 V -15% / +20%
440 V +/- 15%
480 V -10% / +8%
-15% / +10%
50 or 60 Hz, user configurable
40 to 72 Hz
3 phases + N + PE or
3 phases + PE as an option
0.99
11
See section
and Table
30 kW: < 4,5%
40-200 kW: < 3%
10 A/s (default), configurable.
Min 1A/s
Yes, for rectifier and bypass lines
9PHD 30-160 kW with
increased overload capabili-
ty
3 phases + N + PE or
3 phases + PE as an
option
220/380 V; 230/400 V;
240/415 V; 254/440;
277/480 V, configurable.
208–690 V available with
optional transformers
50 or 60 Hz, user
configurable
< 1%
< 5%