Eaton Powerware 9390 Installation And Operation Manual page 169

20-80kva
Hide thumbs Also See for Powerware 9390:
Table of Contents

Advertisement

Table N. Power Cable Conduit Requirements (Cont'd)
UPS Model
Voltage
208/220
Powerware
AC
9390-40/40
and
9390-80/40
DC
480
Powerware
AC
9390-40/40
and
9390-80/40
DC
208/220
AC
Powerware
9390-80/50
DC
480
AC
Powerware
9390-80/50
DC
EATON Powerware
Terminal
AC Input to UPS
(A, B, C, Gnd)
AC Input to Bypass
(A, B, C, Neut, Gnd)
Output
(A, B, C, Neut, Gnd)
Battery
(Positive), (Negative), Gnd
AC Input to UPS
(A, B, C, Gnd)
AC Input to Bypass
(A, B, C, Neut, Gnd)
Output
(A, B, C, Neut, Gnd)
Battery
(Positive), (Negative), Gnd
AC Input to UPS
(A, B, C, Gnd)
AC Input to Bypass
(A, B, C, Neut, Gnd)
Output
(A, B, C, Neut, Gnd)
Battery
(Positive), (Negative), Gnd
AC Input to UPS
(A, B, C, Gnd)
AC Input to Bypass
(A, B, C, Neut, Gnd)
Output
(A, B, C, Neut, Gnd)
Battery
(Positive), (Negative), Gnd
DESCRIPTION:
DRAWING NO:
REVISION:
®
9390 UPS (20–80 kVA) Installation and Operation Manual
Number of
Minimum Conduit
Wires in
Trade Size (inches)
Conduit
4
2‐1/2
5
2‐1/2
5
2‐1/2
3
1
4
1‐1/4
5
1‐1/4
5
1‐1/4
3
1
4
2‐1/2
5
2‐1/2
5
2‐1/2
3
1‐1/2
4
1‐1/2
5
1‐1/2
5
1‐1/2
3
1‐1/2
POWER WIRING INSTALLATION NOTES
164201603-5
DATE:
B
S
164201603 Rev 2 www.powerware.com
INSTALLATION INFORMATION
Number of
Conduits
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
SHEET:
11 of 23
110106
A-21

Advertisement

Table of Contents
loading

Table of Contents