INSTALLATION INFORMATION
1.
Use Class 1 wiring methods (as defined by the NEC) for power wiring.
2.
Use Class 2 wiring methods (as defined by the NEC) for interface wiring from 30 to 600V.
3.
When installing external interface wiring (for example, building alarm, relay output, battery
breaker trip, and X-Slot) to the UPS interface terminals, conduit must be installed
between each device and the UPS cabinet. Install the interface wiring in separate conduit
from the power wiring.
4.
When installing internal interface wiring to X-Slot terminals, route the wiring through the
internal opening in the X-Slot communication bay.
5.
All building alarm inputs or remote features require an isolated normally‐open contact or
switch (rated at 24 Vdc, 20 mA minimum) connected between the alarm input and
common terminal as shown. All control wiring and relay and switch contacts are
customer‐supplied. Use twisted‐pair wires for each alarm input and common.
6.
The building alarms can be programmed to display the alarm functional name.
7.
See Table W through Table AC and Chapters 4, 5, and 6 for customer interface wiring.
8.
LAN and telephone drops for use with X-Slot connectivity cards must be provided by
facility planners or the customer.
Table W. TB1 and TB2 Interface Connections
Terminal TB1
1
2
3
4
5
6
7
8
9
10
Terminal TB2
1
2
3
4
5
6
7
8
9
10
NOTE: "RETURN" INDICATES CONNECTION TO ELECTRONICS CIRCUIT GROUND. "COMMON" INDICATES CONNECTION
TO COMMON SIDE OF ISOLATED RELAY CONTACT.
A-42
EATON Powerware
Name
Remote EPO NC
Remote EPO Return
Remote EPO NO
Remote EPO Return
Batt Breaker Aux
Batt Breaker Aux Return
Battery UVR (+)
Battery UVR (-)
Building Alarm 1
Building Alarm 1 Return
Name
Building Alarm 2
Building Alarm 2 Return
On Bypass NO
On Bypass Common
Alarm Relay NC
Alarm Relay Common
Alarm Relay NO
Alarm Relay Common
On Inverter NC
On Inverter Common
®
9390 UPS (20–80 kVA) Installation and Operation Manual
Input: Normally‐closed dry contact to activate EPO of UPS
from a remote switch
Input: Normally‐open dry contact to activate EPO of UPS
from a remote switch
Input: Normally‐open contact to indicate when UPS UVR
battery breaker is open.
Output: Fused 48 Vdc source to control operation of Battery
Breaker UVR function.
Input: Programmable UPS alarm, activated by a remote dry
contact closure.
Input: Programmable UPS alarm, activated by a remote dry
contact closure. Dedicated for Pull Chain function when part
of Parallel System.
Output: Normally‐open contact closes when UPS is on
bypass. Dedicated for Pull Chain function when part of
Parallel System.
Output: General purpose normally‐closed relay contact.
Output: General purpose normally‐open relay contact.
Output: Normally‐closed contact opens when output
contactor closes.
DESCRIPTION:
INTERFACE WIRING INSTALLATION
NOTES AND TERMINAL LOCATIONS
DRAWING NO:
164201603-8
REVISION:
B
S
164201603 Rev 2 www.powerware.com
Description
Description
SHEET:
DATE:
032406
1 of 15