Ups System Output - Eaton 93PS-8(20)-20(-C) User And Installation Manual

93ps 8–40 kw
Table of Contents

Advertisement

Eaton 93PS UPS 8–40 kW
Number of input phases (rectifier & bypass) 3 phases, N
Input power factor
Rated mains input current
Maximum mains input current
Input current distortion at rated input cur-
rent, iTHD
Rectifier ramp-up, rectifier start and load
step
Backfeed protection
9.3
Number of output phases
Rated output voltage
Rated output frequency
Total voltage harmonic distortion:
100 % linear load
100 % non-linear load
Output frequency variation
Slew rate
Output current
Overload capability at ambient 40 °C (in
the double conversion mode)
Overload capability at ambient 40 °C (in
the stored energy mode)
Overload capability at ambient 40 °C (in
the bypass mode)
©
Eaton Corporation plc 2016. All rights reserved.

UPS system output

0.99
10
See Table
8 kW, 10 kW: resistive load <3%, non-line-
ar load <5%
15–40 kW: resistive load <3%, non-linear
load <4%
10 A/s (default), configurable.
Min 1A/s
Yes, for rectifier and bypass lines
3 phases, N
220/380 V; 230/400 V; 240/415 V, configu-
rable
50 or 60 Hz, user configurable
< 1.5%
< 3.5%
+/- 0.1 Hz (with 1 UPM), +/- 0.15 Hz (with 2
UPMs)
1 Hz/s
10
See Table
102 – 110 % rated power for 10 min
111 – 125 % rated power for 60 s
126 – 150 % rated power for 10 s
> 150% rated power for 300 ms
102 – 110 % rated power for 10 min
111 – 125 % rated power for 60 s
126 – 150 % rated power for 10 s
> 150% rated power for 300 ms
Continuous ≤ 125% load
Transient ≤ 1000% RMS current for 20 ms
Note! Bypass fuses may limit the overload
capability
Revision: 003
Document ID: P-164000493
User's and installation guide
99 (104)