Eaton Powerware 9390 Installation And Operation Manual page 170

20-80kva
Hide thumbs Also See for Powerware 9390:
Table of Contents

Advertisement

INSTALLATION INFORMATION
Table N. Power Cable Conduit Requirements (Cont'd)
UPS Model
Powerware
9390-80/60
Powerware
9390-80/60
Powerware
9390-80/80
Powerware
9390-80/80
A-22
EATON Powerware
Voltage
Terminal
AC Input to UPS
(A, B, C, Gnd)
AC Input to Bypass
208/220
(A, B, C, Neut, Gnd)
AC
Output
(A, B, C, Neut, Gnd)
Battery
DC
(Positive), (Negative), Gnd
AC Input to UPS
(A, B, C, Gnd)
380/
AC Input to Bypass
415/
(A, B, C, Neut, Gnd)
480
AC
Output
(A, B, C, Neut, Gnd)
Battery
(Positive), (Negative), Gnd
DC
AC Input to UPS
(A, B, C, Gnd)
AC Input to Bypass
208/220
(A, B, C, Neut, Gnd)
AC
Output
(A, B, C, Neut, Gnd)
Battery
(Positive), (Negative), Gnd
DC
AC Input to UPS
(A, B, C, Gnd)
380/
AC Input to Bypass
415/
(A, B, C, Neut, Gnd)
480
AC
Output
(A, B, C, Neut, Gnd)
Battery
DC
(Positive), (Negative), Gnd
®
9390 UPS (20–80 kVA) Installation and Operation Manual
Number of
Wires in
Conduit
4
5
5
3
4
5
5
3
4
5
5
3
4
5
5
3
DESCRIPTION:
POWER WIRING INSTALLATION NOTES
DRAWING NO:
164201603-5
REVISION:
B
S
164201603 Rev 2 www.powerware.com
Minimum Conduit
Number of
Trade Size (inches)
Conduits
2‐1/2
2‐1/2
2‐1/2
1‐1/2
2
2
2
1‐1/2
2‐1/2
2‐1/2
2‐1/2
2
2‐1/2
2‐1/2
2‐1/2
2
SHEET:
DATE:
110106
1
1
1
1
1
1
1
1
2
2
2
1
1
1
1
1
12 of 23

Advertisement

Table of Contents
loading

Table of Contents