Eaton Powerware 9390 Installation And Operation Manual page 159

20-80kva
Hide thumbs Also See for Powerware 9390:
Table of Contents

Advertisement

Table E. INPUT/OUTPUT Ratings & External Wiring Requirements for the Powerware 9390-40/20
Basic Unit Rating at 0.9 lagging
pF load
Input and Bypass Input
Output
AC Input to UPS Rectifier
(0.98 min. pF)
Full Load Current plus Battery
Recharge Current
(3) Phases, (1) Ground
Minimum Conductor Size
Number per Phase
AC Input to UPS Bypass
Full Load Current
(3) Phases, (1) Neutral-if required,
(1) Ground
Minimum Conductor Size
Number per Phase
DC Input from Battery to UPS
(1) Positive, (1) Negative
Minimum Conductor Size
Number per Pole
AC Output to Critical Load
Full Load Current
(3) Phases, (1) Neutral-if required,
(1) Ground
Minimum Conductor Size
Number per Phase
Neutral Bonding Jumper
Minimum Conductor Size
Number (See Note 7)
NOTE
Callout letters A , B , C , and D map to Drawing 164201603-4, sheets 1 of 5,
3 of 5, 4 of 5, and 5 of 5.
Read and understand the following notes while planning and performing the installation:
1.
Refer to national and local electrical codes for acceptable external wiring practices.
2.
Material and labor for external wiring requirements are to be provided by designated
personnel.
3.
For external wiring, use 90C copper wire. See the appropriate information in Table E
through Table J. Wire sizes are based on using the specified breakers.
4.
Wire ampacities are chosen from Table 310-16 of the NEC. Wire is 90C specification.
5.
If installing, as part of the UPS system, a maintenance bypass without a rectifier input
breaker, a minimum of two separate feeds with upstream feeder breakers, or one feed with
two upstream feeder breakers, must be provided: one for the UPS and one for the
maintenance bypass input. DO NOT use one feed or a single‐feeder breaker to supply
both the UPS and the maintenance bypass.
EATON Powerware
Units
kVA
kW
VOLTS
208/220
VOLTS
208/220
Amps
A
AWG or kcmil
(each)
Amps
B
AWG or kcmil
(each)
Vdc
384-480
Amps@
(2.0V/cell)
C
AWG or kcmil
(each)
Amps
D
AWG or kcmil
(each)
AWG or kcmil
-
(each)
DESCRIPTION:
DRAWING NO:
REVISION:
®
9390 UPS (20–80 kVA) Installation and Operation Manual
Rating 50/60 Hz
20
20
20
18
18
18
380
400
380
400
60
34
33
2
6
(1)
(1)
(1)
56/53
31
29
2
6
(1)
(1)
(1)
432-480
432-480
51
51
51
2
2
(1)
(1)
(1)
56/53
31
29
2
6
(1)
(1)
(1)
4
6
(1)
(1)
(1)
POWER WIRING INSTALLATION NOTES
164201603-5
DATE:
D
S
164201603 Rev 2 www.powerware.com
INSTALLATION INFORMATION
20
20
18
18
415
480
415
480
32
30
6
6
6
(1)
(1)
28
24
6
6
6
(1)
(1)
432-480
432-480
51
51
2
2
2
(1)
(1)
28
24
6
6
6
(1)
(1)
6
6
6
(1)
(1)
SHEET:
1 of 23
071608
A-11