Eaton Powerware 9390 Installation And Operation Manual page 193

20-80kva
Hide thumbs Also See for Powerware 9390:
Table of Contents

Advertisement

MINI‐CSB INTERFACE TERMINALS
P5
NOTE
1. All building alarm inputs require an isolated normally‐open or
normally‐closed contact or switch (rated at 24 Vdc, 20 mA minimum)
connected between the alarm input and common terminal as shown.
Building alarm inputs can be programmed for use with either normally‐open
or normally‐closed contacts. All control wiring and relay and switch contacts
are customer‐supplied.
2. The building alarms can be programmed to display the alarm functional
name.
EATON Powerware
®
9390 UPS (20–80 kVA) Installation and Operation Manual
MINI‐CSB
1
8
DESCRIPTION:
INTERFACE WIRING INSTALLATION
NOTES AND TERMINAL LOCATIONS
DRAWING NO:
164201603-8
REVISION:
A
INSTALLATION INFORMATION
BUILDING ALARM
#3
BUILDING ALARM #3 RTN
BUILDING ALARM
#4
BUILDING ALARM #4 RTN
BUILDING ALARM
#5
BUILDING ALARM #5 RTN
BUILDING ALARM
#6
BUILDING ALARM #6 RTN
SHEET:
DATE:
091505
S
164201603 Rev 2 www.powerware.com
4 of 15
A-45

Advertisement

Table of Contents
loading

Table of Contents