Normal Mode - Rt; Figure 7-2. Path Of Current Through The Ups In Normal Mode - Rt - Eaton Powerware 9390 Installation And Operation Manual

20-80kva
Hide thumbs Also See for Powerware 9390:
Table of Contents

Advertisement

7.1.2
Normal Mode – RT
Figure 7‐2 shows the path of electrical power through the UPS system when the UPS
is operating in Normal mode.
Rectifier
Rectifier
K1
K1
Breakers
Breakers
Contactors
Contactors
Closed
Closed
Open
Open
During normal UPS operation, power for the system is derived from a utility input
source through the rectifier input contactor K1. The front panel displays "Normal,"
indicating the incoming power is within voltage and frequency acceptance windows.
Three-phase AC input power is converted to DC using IGBT devices to produce a
regulated DC voltage to the inverter. The battery is charged directly from the
regulated rectifier output through a buck or boost DC converter, depending on
whether the system is 208V, 380V, 400V, 415V, or 480V and the size of the battery
string attached to the unit.
The battery converter derives its input from the regulated DC output of the rectifier
and provides either a boosted or bucked regulated DC voltage charge current to the
battery. The UPS monitors the battery charge condition and reports the status on the
control panel. The battery is always connected to the UPS and ready to support the
inverter should the utility input become unavailable.
®
EATON Powerware
9390 UPS (20–80 kVA) Installation and Operation Manual
Static
Static
K5
K5
Switch
Switch
Battery
Battery
Converter
Converter
Battery
Battery
Breaker
Breaker
Battery
Battery
Figure 7‐2. Path of Current Through the UPS in Normal Mode – RT
UNDERSTANDING UPS OPERATION
Inverter
Inverter
Main Power Flow
Main Power Flow
Trickle Current
Trickle Current
Energized
Energized
De-Energized
De-Energized
S
164201603 Rev 2 www.powerware.com
K3
K3
7-3

Advertisement

Table of Contents
loading

Table of Contents