Eaton Powerware 9390 Installation And Operation Manual page 167

20-80kva
Hide thumbs Also See for Powerware 9390:
Table of Contents

Advertisement

Table M. UPS Cabinet Power Cable Terminations for the Powerware 9390-80/40,
9390-80/50, 9390-80/60, and 9390-80/80 (380V/400V/415V/480V Input and
380V/400V/415V/480V Output)
Terminal Function
AC Input to UPS Rectifier
and Bypass
(Single Input)
AC Input to UPS Rectifier
(Dual Input)
AC Input To Bypass
(Dual Input)
Single‐Feed To Dual‐Feed
Remove Jumpers between
Rectifier Input Terminals
and Bypass Input
Terminals
AC Output to
Critical Load
DC Input from
Battery to UPS
Input and Output Neutral
Customer Ground
NOTE
Customer ground can be run in any conduit listed in Table N.
EATON Powerware
Size of Pressure
Terminal Function
E6
Phase A
E7
Phase B
E8
Phase C
E1
Phase A
E2
Phase B
E3
Phase C
E6
Phase A
E7
Phase B
E8
Phase C
Phase A
Phase B
Phase C
E9
Phase A
E10
Phase B
E11
Phase C
E4
Positive
1 - #6-350 kcmil
E5
Negative
1 - #6-350 kcmil
E12
Neutral
Ground
Ground
DESCRIPTION:
DRAWING NO:
REVISION:
®
9390 UPS (20–80 kVA) Installation and Operation Manual
Tightening
Torque
Termination
Nm (lb in)
13.5 (120)
1 - #14-2/0
13.5 (120)
1 - #14-2/0
1 - #14-2/0
13.5 (120)
1 - #14-2/0
13.5 (120)
1 - #14-2/0
13.5 (120)
1 - #14-2/0
13.5 (120)
13.5 (120)
1 - #14-2/0
1 - #14-2/0
13.5 (120)
1 - #14-2/0
13.5 (120)
N/A
5.6 (50)
N/A
5.6 (50)
N/A
5.6 (50)
13.5 (120)
1 - #14-2/0
13.5 (120)
1 - #14-2/0
1 - #14-2/0
13.5 (120)
31.1 (275)
31.1 (275)
4 - #14-1/0
5.6 (50)
8 - #14-1/0
5.6 (50)
POWER WIRING INSTALLATION NOTES
164201603-5
DATE:
C
S
164201603 Rev 2 www.powerware.com
INSTALLATION INFORMATION
Type
Screw
3/16 in. Hex
3/16 in. Hex
3/16 in. Hex
3/16 in. Hex
3/16 in. Hex
3/16 in. Hex
3/16 in. Hex
3/16 in. Hex
3/16 in. Hex
1/4–20 Hex Nut
1/4–20 Hex Nut
1/4–20 Hex Nut
3/16 in. Hex
3/16 in. Hex
3/16 in. Hex
5/16 in. Hex
5/16 in. Hex
Slotted
Slotted
SHEET:
9 of 23
071608
A-19