Eaton Powerware 9390 Installation And Operation Manual page 172

20-80kva
Hide thumbs Also See for Powerware 9390:
Table of Contents

Advertisement

INSTALLATION INFORMATION
Table N. Power Cable Conduit Requirements (Cont'd)
UPS Model
Powerware
9390 80/60
Powerware
9390 80/80
A-24
EATON Powerware
Voltage
Terminal
AC Input to UPS
(A, B, C, Gnd)
380/
AC Input to Bypass
400/
(A, B, C, Neut, Gnd)
415
AC
Output
(A, B, C, Neut, Gnd)
Battery
DC
(Positive), (Negative), Gnd
AC Input to UPS
(A, B, C, Gnd)
380/
AC Input to Bypass
400/
(A, B, C, Neut, Gnd)
415
AC
Output
(A, B, C, Neut, Gnd)
Battery
(Positive), (Negative), Gnd
DC
®
9390 UPS (20–80 kVA) Installation and Operation Manual
Number of
Wires in
Conduit
4
5
5
3
4
5
5
3
DESCRIPTION:
POWER WIRING INSTALLATION NOTES
DRAWING NO:
164201603-5
REVISION:
C
S
164201603 Rev 2 www.powerware.com
Minimum Conduit
Number of
Trade Size (inches)
Conduits
2‐1/2
2‐1/2
2‐1/2
2
2‐1/2
2‐1/2
2‐1/2
2
SHEET:
DATE:
071608
1
1
1
1
1
1
1
1
14 of 23

Advertisement

Table of Contents
loading

Table of Contents